Bidhelp
E-IN-C BRANCH - MILITARY ENGINEER SERVICES||CE SC AND CE PUNE ZONE - MES||CWE (ARMY) MUMBAI - MES||GE (WEST) COLABA - MES
E-IN-C BRANCH - MILITARY ENGINEER SERVICES||CE SC AND CE PUNE ZONE - MES||CWE (ARMY) MUMBAI - MES||GE (WEST) COLABA - MES
Kameshwar Prasad, IDSE, EE
Maharashtra QTY :

Items - REPAIR/MAINT OF LIGHTING PROTECTION SYSTEM AND OTHER CONNECTED ITEMS OF HIGH RISE BLDG UNDER GE (W) COLABA

Tender Details
Costs
Documents
BOQ

BoQ1

Item Rate BoQ
BoQ_Ver4.0Item RateNormalINR OnlyINR
Select, Excess (+), Less (-)Less (-)
Tender Inviting Authority: GARRISON ENGINEER (WEST) COLABA MUMBAI
Name of Work: Repair/Maint of lighting protection system and other connected items of high rise Bldg under GE (W) Colaba
File No : 8112/E8
Name of the Bidder/ Bidding Firm / Company :
PRICE SCHEDULE (This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only)
Sl. No.Item DescriptionItem Code / MakeQuantityUnitsEstimated RateAddition / DeductionAddition / Deduction ValuesCurrency Convertion against each ItemQuoted Currency in INR / Other CurrencyBASIC RATE In Figures To be entered by the Bidder Rs. P Excise DutyVATFreight Charges ( Unloading & Stacking)Any Other Taxes/Duties/LeviesOther Taxes 2IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service TaxLess for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNTTOTAL AMOUNT With TaxesTOTAL AMOUNT In Words
12334678910111251415161718192021222324252627282930313233343536373839404142434445464748495051526547
1.00M&L fixedin repair Aluminum strip 25x3.15 mm earth continuity conductor or Main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles in roof of high rise bldg or any other indicated and as required by sadles not more than distatance of 50 cm between two saddles with jointing nuts, bolts /washers to wall/surface or recess of high rised buildings or burried in ground or any situation for loop, complete all as specified and directed by the Engineer-in-Charge.itemH1Code11400.00RM0.00Excess(+)1Full ConversionINR0.000.00INR Zero Only1.01Supplying, Conveying and fixing spls. Including eartitem1123.223Nos
2.00M&L fixed in repair Copper strip 20x3.15 mm earth continuity conductor or Main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles in roof of high rise bldg and as required by sadles not more than distatance of 50 cm between two saddles with jointing nuts, bolts /washers to wall/surface or recess of high rised buildings or burried in ground or any situation for loop, complete all as specified and directed by the Engineer-in-Charge.itemH1Code2600.00RM1.00Excess(+)1Full ConversionINR0.000.00INR Zero Only2.01Supplying, Conveying and fixing spls. Including eartitem2124.223Nos
3.00M&L fixed in repair Galvanised iron strip 32x6mm earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles in roof of high rise bldg and as required by sadles not more than distatance of 50 cm between two saddles with jointing nuts, bolts /washers to wall/surface or recess of high rised buildings or burried in ground or any situation for loop, complete all as specified and directed by the Engineer-in-Charge.itemH1Code31000.00RM2.00Excess(+)1Full ConversionINR0.000.00INR Zero Only3.01Supplying, Conveying and fixing spls. Including eartitem3125.223Nos
4.00M&L for repair of Single pointed air termination aluminium rod 12 mm dia 300mm long complete to walls/roof/pipes with suitable clamps of MS bolts and nuts etc required at site, complete all as specified and as directed by Engineer-in-Charge. (MS work will be measured and paid separately).itemH1Code4200.00Each3.00Excess(+)1Full ConversionINR0.000.00INR Zero Only4.01Supplying, Conveying and fixing spls. Including eartitem4126.223Nos
5.00M&L for repair of Single pointed air termination Copper rod 12 mm dia 300mm long complete to walls/roof/pipes with suitable clamps of MS bolts and nuts etc required at site. Complete all as specified and as directed by Engineer-in-Charge. (MS work will be measured and paid separately).itemH1Code550.00Each4.00Excess(+)1Full ConversionINR0.000.00INR Zero Only5.01Supplying, Conveying and fixing spls. Including eartitem5127.223Nos
6.00M & L replacement of 3 core copper conductor of Size 4 Sqmm for obstruction light in over head tank/high rise tower/ bldg including 20mm PVC pipe and sadles etc. not more than distatance of 50 cm between two saddles, complete all as specified and directed by Engineer-in-Charge.itemH1Code6500.00RM5.00Excess(+)1Full ConversionINR0.000.00INR Zero Only6.01Supplying, Conveying and fixing spls. Including eartitem6128.223Nos
7.00M & L replacement of 3 core copper conductor of Size 6 Sqmm for obstruction light in over head tank/high rise tower/ bldg including 20mm PVC pipe and sadles etc. not more than distatance of 50 cm between two saddles, complete all as specified and directed by Engineer-in-Charge.itemH1Code7500.00RM6.00Excess(+)1Full ConversionINR0.000.00INR Zero Only7.01Supplying, Conveying and fixing spls. Including eartitem7129.223Nos
8.00M&L for copper strip 32x6 mm earth continuity conductor or Main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles in roof of high rise bldg and as required by sadles not more than distatance of 50 cm between two saddles with jointing nuts, bolts /washers to wall/surface or recess of high rised buildings or burried in ground or any situation for loop, complete all as specified and directed by the Engineer-in-Charge.itemH1Code8800.00RM7.00Excess(+)1Full ConversionINR0.000.00INR Zero Only8.01Supplying, Conveying and fixing spls. Including eartitem8130.223Nos
9.00Replacement of Gl tubing 40mm bore light grade in trenches/ floor/ fixed along pole for cable/earth strip protection with proper size of clamps nuts and bolts for fixing lighting conductor etc, complete all as specified and directed by the Engineer-in-Charge. itemH1Code9200.00RM8.00Excess(+)1Full ConversionINR0.000.00INR Zero Only9.01Supplying, Conveying and fixing spls. Including eartitem9131.223Nos
10.00All as per Srl No. 9 above but of size 50mm bore.itemH1Code10100.00RM9.00Excess(+)1Full ConversionINR0.000.00INR Zero Only10.01Supplying, Conveying and fixing spls. Including eartitem10132.223Nos
11.00Test Point terminal block made of gunmetal or phosphorus bronze size 75X75X25mm drilled and screwed including 03 Nos 8 mm dia long hex head screw, complete all as specified and directed by Engineer-in-Charge.itemH1Code11110.00Each10.00Excess(+)1Full ConversionINR0.000.00INR Zero Only11.01Supplying, Conveying and fixing spls. Including eartitem11133.223Nos
12.00Replacement of Earthing complete with galvanized steel earth plate electrode 600 x 600 mm, thickness not less than 6mm buried directly in ground (earth pit not less than 2.25 mtr deep Below ground level) with top edge of the plate not less than 1.5 mtr below ground level, connected to galvanized earth lead 25 x 3.15 mm dia by means of bolts, nuts, check nuts and washers of GI including PCC pit in PCC 1:2:4 type B-1 angle iron 40x40x3mm frame with pre-cast RCC 1:2:4 type B-1 cover with XPM weight not less than 4kg/sqm and 6mm dia bar handle, excavation and earth work in any type of soil, charcoal, dust and common salt light grade GI watering pipe 20mm bore with funnel and wire mesh and light grade GI protection pipe 15mm bore 5 mtr long and earth wire up to main earthing of pole complete all as shown in Electric Plate No 3 of SSR 2009 Part-I, to achieve earthing resistance within 1 Ohm all as specified and testing on, completion all as specified and directed.itemH1Code1260.00Each11.00Excess(+)1Full ConversionINR0.000.00INR Zero Only12.01Supplying, Conveying and fixing spls. Including eartitem12134.223Nos
13.00All as per Srl item No. 12 above but using galvanised iron strip 32x6mm upto test point.itemH1Code1360.00Each12.00Excess(+)1Full ConversionINR0.000.00INR Zero Only13.01Supplying, Conveying and fixing spls. Including eartitem13135.223Nos
14.00M & L for Earthing complete with Copper earth plate electrode 600 x 600 mm, thickness n.less than 6mm buried directly in ground (earth pit not less than 2.25 mtr deep Below ground level) with top edge of the plate n.less than 1.5 mtr below ground level, connected to copper earth lead 25 x 3.15 mm dia by means of bolts, nuts, check nuts and washers of GI including PCC pit in PCC 1:2:4 type B-1 angle iron 40x40x3mm frame with pre-cast RCC 1:2:4 type B-1 cover with XPM weight n.less than 4kg/sqm and 6mm dia bar handle, excavation and earth work in any type of soil, charcoal, dust and common salt light grade GI watering pipe 20mm bore with funnel and wire mesh and light grade GI protection pipe 15mm bore 05 mtr long and earth wire up to main earthing of pole complete all as shown in Electric Plate No 3 of SSR 2009 Part-I, to achieve earthing resistance within 1 Ohm all as specified and testing on, completion all as specified and directed.itemH1Code1416.00Each13.00Excess(+)1Full ConversionINR0.000.00INR Zero Only14.01Supplying, Conveying and fixing spls. Including eartitem14136.223Nos
15.00S&F Cross arms bracing supports clamps and back plates fabricated from structural steel section including nut, bolts, washers, welded, binding, cold as hot drilling holes for bolts in any shape or size as required painted with two coats of aluminium paint over a coat of red oxide primer after preparation of surface, including taking out old, complete all as specified and directed by the Engineer-in-Charge.itemH1Code151.00Qtl14.00Excess(+)1Full ConversionINR0.000.00INR Zero Only15.01Supplying, Conveying and fixing spls. Including eartitem15137.223Nos
16.00S&F in repair Metal plug clad & socket including MCB SPN 20 Amps, complete all as specified and directed by the Engineer-in-Charge.itemH1Code1620.00Each15.00Excess(+)1Full ConversionINR0.000.00INR Zero Only16.01Supplying, Conveying and fixing spls. Including eartitem16138.223Nos
17.00M&L for repair galvanised iron strip 25x3.15mm earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or or buried in ground or drawn in conduit/pipe or fixed to poles in roof of high rise bldg and as required by sadles not more than distatance of 50 cm between two saddles with jointing nuts, bolts /washers to wall/surface or recess of high rised buildings or burried in ground or any situation for loop, complete all as specified and directed by the Engineer-in-Charge.itemH1Code171400.00RM16.00Excess(+)1Full ConversionINR0.000.00INR Zero Only17.01Supplying, Conveying and fixing spls. Including eartitem17139.223Nos
18.00M&L of taking down existing aluminum strip 25mmx3.00mm / 32x6mm Gl Strip from the top of bldg /ground (roof down conductor) and keep shape custody (for serviceable strips for re-use ), retrieved, complete all as specified and directed by Engineer-in-Charge.itemH1Code185200.00RM17.00Excess(+)1Full ConversionINR0.000.00INR Zero Only18.01Supplying, Conveying and fixing spls. Including eartitem18140.223Nos
19.00M&L Making old serviceable strips refined against item no-18 making straight and re-fixing the same in position by wiring screw / gattas /insulators /PCC Block, complete all as specified and directed by Engineer-in-charge.itemH1Code191500.00RM18.00Excess(+)1Full ConversionINR0.000.00INR Zero Only19.01Supplying, Conveying and fixing spls. Including eartitem19141.223Nos
20.00M&L for Raw salt with mixing in water for existing earthing, complete all as specified and directed by the Engineer-in-Charge.itemH1Code20500.00Kg19.00Excess(+)1Full ConversionINR0.000.00INR Zero Only20.01Supplying, Conveying and fixing spls. Including eartitem20142.223Nos
21.00M&L Funnel suitable for each pit, complete all as specified and directed by the Engineer-in-Charge. itemH1Code21100.00Each 20.00Excess(+)1Full ConversionINR0.000.00INR Zero Only21.01Supplying, Conveying and fixing spls. Including eartitem21143.223Nos
22.00M&L for repair insulator for each strip and fixed arrangement in roof/wall of building for run of strips on it with nuts and bolts, complete all as specified and directed by the Engineer-in-Charge.itemH1Code221500.00Each21.00Excess(+)1Full ConversionINR0.000.00INR Zero Only22.01Supplying, Conveying and fixing spls. Including eartitem22144.223Nos
23.00M&L dismantling of PCC earth pit chamber and making PCC chamber of size as per electrical plate No 3 of SSR 2009 Part I with PCC (1:2:4) type B1 including RCC cover with suitable handle, complete all as specified and directed by the Engineer-in-Charge.itemH1Code2360.00Each22.00Excess(+)1Full ConversionINR0.000.00INR Zero Only23.01Supplying, Conveying and fixing spls. Including eartitem23145.223Nos
24.00M&L in replacement of Pit cover, Cl 10mm thick hinged to Cl frame 40x40mm, complete all as specified and directed by the Engineer-in-Charge.itemH1Code2460.00Each23.00Excess(+)1Full ConversionINR0.000.00INR Zero Only24.01Supplying, Conveying and fixing spls. Including eartitem24146.223Nos
25.00M & L for in replacement of LED Aviation obstruction light 10w over head tanks / Bldg / high mast/Saft pans are as following : (a) Luminaries body : Aviation yellow colored die-cast aluminum alloy housing10 watt. (b) Enclosure : Red colored poly carbonate done secured to housing by 3 Nos screw. (c) Mounting arrangement : 38 mm dia threaded item with lock nets for mounting on pipe above structure. (d) Degree of protection : IP43. (e) GI Pipe 3mtr long with nut bolt clmap and PCC foundation for fixing pipe and light, complete all as specified and directed.itemH1Code2515.00Each24.00Excess(+)1Full ConversionINR0.000.00INR Zero Only25.01Supplying, Conveying and fixing spls. Including eartitem25147.223Nos
26.00M & L replacement of 2 core copper conductor of Size 2.5 Sqmm for obstruction light in over head tank/high rise tower/ bldg including 20mm pvc pipe and sadles etc. not more than distatance of 50 cm between two saddles, complete all as specified and directed by Engineer-in-Charge.itemH1Code261000.00RM25.00Excess(+)1Full ConversionINR0.000.00INR Zero Only26.01Supplying, Conveying and fixing spls. Including eartitem26148.223Nos
27.00Material and labour and replacement for Maintenance free Chemical Earthing comprising of 17.2 mm dia molecularly copper bounded 250mm micron on steel electrode 2.5 mtr long each- 03 Nos, earth enhacning soil treatment compound having essential chemical ingradinets such as ionic chemical, dispersion chemical, diffusion chemcial, expansion chemical and bygroscopic chemical to provide stable low resistance for earth terminal to make it maintenance free (25 kg per beg x 3 beg required per set of chmical earthing) HDPE earth pit cover madium duty to withstand 2000 kg load U clamp bolt for connecting copper strp Mimimum size of copper strip 25 X 3 mm-20RM to earth rod and connection, complete all as specified and directed.itemH1Code2730.00Each Job 26.00Excess(+)1Full ConversionINR0.000.00INR Zero Only27.01Supplying, Conveying and fixing spls. Including eartitem27149.223Nos
28.00M&L sheet metal enclosure 2 way with MCB SPN 16 Amps fixed in high rise bldg, complete all as specified and directed by Engineer-in-Charge.itemH1Code2860.00Each27.00Excess(+)1Full ConversionINR0.000.00INR Zero Only28.01Supplying, Conveying and fixing spls. Including eartitem28150.223Nos
29.00M&L for replacement in repair refilling of earthing materials charcoal, salt in sufficient quantities at par the satisfaction of Engr - in- Charge for better results in existing earthing, complete all as specified and directed by Engineer-in-Charge.itemH1Code2920.00Each Job 28.00Excess(+)1Full ConversionINR0.000.00INR Zero Only29.01Supplying, Conveying and fixing spls. Including eartitem29151.223Nos
30.00Material and labour for Sub main wiring, with two run of 2.5 sq mm stranded copper conductor PVC unsheathed FRLSH wire along with 2.5 sq mm green colour wire as earth contuinity conductor connected to common earth dolly including PVC FR heavy duty conduit of adequate size (not less than 32 mm dia) for housing the wires including taking down old unserviceable submain with all associated fixtures, complete all as specified and directed by Engineer-in-Charge. Note: Thimble/lugs of rating of MCB should be used with wire for fixing in the MCB. Note: Mode of measurement two runs of 2.5 sqmm cable and one run of 2.5 sqmm cable with PVC conduite shall be measured as one length.itemH1Code30950.00RM29.00Excess(+)1Full ConversionINR0.000.00INR Zero Only30.01Supplying, Conveying and fixing spls. Including eartitem30152.223Nos
31.00S&F in repair for wall mounted fan metal body having high speed of sweep size 450 mm, with nuts bolts, fastners including connecting with PVC insulated and PVC sheathed copper flexible cable and necessary fixing arrangement, complete all as specified and directed by Engineer-in-Charge.itemH1Code3111.00Each30.00Excess(+)1Full ConversionINR0.000.00INR Zero Only31.01Supplying, Conveying and fixing spls. Including eartitem31153.223Nos
32.00Supply, lay in repair trenches, floors, fix on wall/pole, LT UG cable, 1100 volts grade, PVC insulated, with multistranded Copper conductors, armoured with galvanised steel wire or tape, gland, copper lugs etc, of size 10 Sqmm 3 core, confirming to IS specifications suitable for LT panel to motor pump connection including clamp, nut bolt, passing through 20/25mm pipes etc., including cutting of wall / flooring etc with making good sarface, complete all as specified and directed.itemH1Code321000.00RM31.00Excess(+)1Full ConversionINR0.000.00INR Zero Only32.01Supplying, Conveying and fixing spls. Including eartitem32154.223Nos
33.00S&F in repair monoblock pump 0.5 HP with suitable size sensor for auto cat, with nuts bolts, union, pipe for fixing connecting with PVC insulated and PVC sheathed copper flexible cable and necessary fixing arrangement, complete all as specified and directed.itemH1Code3310.00Each32.00Excess(+)1Full ConversionINR0.000.00INR Zero Only33.01Supplying, Conveying and fixing spls. Including eartitem33155.223Nos
34.00M&L for Sub main wiring in repair, with two runs of 16 sqmm stranded copper conductor PVC unsheathed FRLSH wire along with 16 sqmm green colour wire as earth continuity conductor connected to common earth dolly including PVC FR heavy duty conduit of adequate size (not less than 32 mm dia) for housing the wires from panel / Main DB to house SPN DB, with all associated fixtures, complete all as specified & directed by Engr-in-Charge. Note: Thimble/lugs of rating of MCB should be used with wire for fixing in the MCB. Note: Mode of measurement two runs of 16 sqmm cable and one run of 16 sqmm cable with PVC conduite shall be measured as one length.itemH1Code34800.00RM33.00Excess(+)1Full ConversionINR0.000.00INR Zero Only34.01Supplying, Conveying and fixing spls. Including eartitem34156.223Nos
35.00all as per item No. 34 above but 10 Sqmm complete.itemH1Code35850.00RM34.00Excess(+)1Full ConversionINR0.000.00INR Zero Only35.01Supplying, Conveying and fixing spls. Including eartitem35157.223Nos
36.00S&F in repair shed water proof 2.5 fit x 2.5 fit x 2.5 fit to protect motor from water including 2 fit PCC from ground, 2mm sheet and 50x50x5mm angle iron frame, wooden frame for fixing monoblock pump 0.5 HP and sensor with suitable size locking arrangement, nuts bolts, union, pipe for fixing connecting pump with PVC copper flexible cable and necessary fixing arrangement, complete all as specified and directed.itemH1Code3620.00Each Job 35.00Excess(+)1Full ConversionINR0.000.00INR Zero Only36.01Supplying, Conveying and fixing spls. Including eartitem36158.223Nos
Total in Figures0.000.00INR Zero Only4Construction of chamber for 100mm sluice platesitem510Nos
Quoted Rate in FiguresSelect0.00000.0000 Zero Only
Quoted Rate in WordsINR Zero Only