Items - REPAIR/ MAINT OF LT PANELS, FEEDER PILLAR BOX AND LT UG CABLES, OH LINES AND OTHER ALLIED WORKS RELATED TO REPAIRS/MAINT OF DIFFERENT TYPE OF BUILDING, PARK SECURITY LIGHTS PANEL AND DRIVER AT TECH RESIDENTIAL AREA AT DEAL UNDER GE (I) RND DEHRADUN
Item Rate BoQ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||
BoQ_Ver3.0 | Item Rate | Normal | INR Only | INR | ||||||||||||||||||||||||||||||||||||||||||||||||||
Select, Excess (+), Less (-) | Less (-) | |||||||||||||||||||||||||||||||||||||||||||||||||||||
TENDER INVITING AUTHORITY: GARRISON ENGINEER (I) R&D DEHRADUN | ||||||||||||||||||||||||||||||||||||||||||||||||||||||
NAME OF WORK : REPAIR/ MAINT OF LT PANELS, FEEDER PILLAR BOX AND LT UG CABLES, OH LINES AND OTHER ALLIED WORKS RELATED TO REPAIRS/MAINT OF DIFFERENT TYPE OF BUILDING, OUTDOOR, PARK AND SECURITY LIGHTS ALONG WITH ITS PANEL AND DRIVER AT TECHNICAL & RESIDENTIAL AREA AT DEAL UNDER GE (I) R&D DEHRADUN | ||||||||||||||||||||||||||||||||||||||||||||||||||||||
CONTRACT No: GE(I)RND/DDN/54 OF 2025-2026 FILE NO: 9498/E8 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||
Bidder Name : | ||||||||||||||||||||||||||||||||||||||||||||||||||||||
PRICE SCHEDULE (This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) | ||||||||||||||||||||||||||||||||||||||||||||||||||||||
Sl. No. | Item Description | Item Code / Make | Quantity | Units | Estimated Rate | Addition / Deduction | Addition / Deduction Values | Currency Convertion against each Item | Quoted Currency in INR / Other Currency | RATE In Figures To be entered by the Bidder Rs. P | Excise Duty | VAT | Freight Charges ( Unloading & Stacking) | Any Other Taxes/Duties/Levies | Other Taxes 2 | IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax | Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category | TOTAL AMOUNT Without Taxes | TOTAL AMOUNT In Figures | Rate In Words | ||||||||||||||||||||||||||||||||||
1 | 2 | 3 | 3 | 4 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | 5 | 14 | 15 | 16 | 17 | 18 | 19 | 20 | 21 | 22 | 23 | 24 | 25 | 26 | 27 | 28 | 29 | 30 | 31 | 32 | 33 | 34 | 35 | 36 | 37 | 38 | 39 | 40 | 41 | 42 | 43 | 44 | 45 | 46 | 47 | 48 | 49 | 50 | 51 | 52 | 53 | 6 | 7 |
1 | Excavation in trenches in any type of soil not exceeding 1.5 metre deep and not exceeding 1.5 mtr width and getting out soil including forming bottom surface to required slope/gradient for laying cables/pipes etc. all as specified and directed by Engineer-in-Charge including removing cable protection covers/ bricks & stacking serviceable bricks for reuse and disposal of unserviceable covers within 50 m complete all as specified and directed by Engineer-in-Charge. Note : (i) Excavation shall be made carefully in order to avoid damage of existing cables and brick protection. (ii) The excavation work may be carried out in short lengths for locating fault in under ground cables at different locations | 225.00 | Cum | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 1.02 | Construction of chamber for 100mm sluice plates | item2 | 213 | Nos | |||||||||||||||||||||||||||||||||||||||
2 | M&L for Returning, filling in including spreading, leveling, watering and well ramming in layers of 25 cm thick after the cables etc. are laid, jointed and tested complete all as specified and directed by Engineer-in-Charge. | 160.00 | Cum | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 1.01 | Supplying, Conveying and fixing spls. Including eart | item1 | 123.223 | Nos | |||||||||||||||||||||||||||||||||||||||
3 | M&L for Removal of surplus excavated soils not exceeding 50 Mtr distance and depositing where directed by Engineer-in-Charge at a level not exceeding 1.5 m above the starting point complete all as specified and directed by Engineer-in-Charge. | 65.00 | Cum | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 1.02 | Construction of chamber for 100mm sluice plates | item2 | 213 | Nos | |||||||||||||||||||||||||||||||||||||||
4 | Material & labour for sand filling with clean dry find sand unwashed including gently punning around cables in trenches/ducts for cable protection complete all as specified and directed by Engineer-in-Charge. | 65.00 | Cum | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 2 | Construction of chamber for 100mm sluices valve | item3 | 10 | Nos | |||||||||||||||||||||||||||||||||||||||
5 | Supplying and laying un-reinforced precast concrete cable cover, class LV, type 1 with flat, size 250 mm x 150mm x 40mm complete all as specified and directed by Engineer-in-Charge. | 4000.00 | Each | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 1.02 | Construction of chamber for 100mm sluice plates | item2 | 213 | Nos | |||||||||||||||||||||||||||||||||||||||
6 | Fixing / laying only old PCC cable cover of any description as obtained from dismantling of the cable complete all as specified and directed by the Engineer-in-Charge. | 1000.00 | Each | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 1.01 | Supplying, Conveying and fixing spls. Including eart | item1 | 123.223 | Nos | |||||||||||||||||||||||||||||||||||||||
7 | Disconnecting and taking out old unserviceable GI pipe and Supplying, laying & jointing GI water tubing, , light grade as in sleeving etc laid in trenches / pole post etc, cutting and making necessaries arangement by means of wedling and jointing suitable for post of larntent/ street light fitting including PCC work complete all as specified and directed of following sizes. (Note : PCC work shall be measured and paid seperatly under Sch "A' relevent item) | 1.02 | Construction of chamber for 100mm sluice plates | item2 | 213 | Nos | ||||||||||||||||||||||||||||||||||||||||||||||||
8 | GI tubing 100 mm dia | 12.00 | RM | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 2 | Construction of chamber for 100mm sluices valve | item3 | 10 | Nos | |||||||||||||||||||||||||||||||||||||||
9 | GI tubing 80 mm dia | 12.00 | RM | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 1.02 | Construction of chamber for 100mm sluice plates | item2 | 213 | Nos | |||||||||||||||||||||||||||||||||||||||
10 | GI tubing 40 mm dia | 24.00 | RM | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 2 | Construction of chamber for 100mm sluices valve | item3 | 10 | Nos | |||||||||||||||||||||||||||||||||||||||
11 | Dismantling & taking out unserviceable steel & iron items from poles and Supply & fixing cross arms, bracing, supports, clamps and back plates fabricated from structural steel sections including nuts & bolts , washers , welding bending cold or hot , drilling holes for bolts in any shape or size as indicated or directed and inclusive of two coats of aluminium paint over a coat of red oxide primer complete all as specified and directed by Engineer-in-Charge. | 0.50 | Qtl | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 1.02 | Construction of chamber for 100mm sluice plates | item2 | 213 | Nos | |||||||||||||||||||||||||||||||||||||||
12 | Disconnecting and taking out old existing unserviceable/ non- functional LT Cable and Supplying, laying, jointing and testing cable XLPE insulated IS 7098 (Part-I)-1988 marked, screened, PVC sheathed, armoured electric power cable (heavy duty) with aluminum conductor for working voltage upto and including 1100 Volts, cross sectional area of under mentioned size of cables laid in trenches/fixed on pole/wall / passed through pipe complete all as specified and directed by Engineer-in-Charge. (NOTE: Earth work, sand cushioning, pipe, clamps for holding cables and brick protection shall be measured and paid separately ) | 2 | Construction of chamber for 100mm sluices valve | item3 | 10 | Nos | ||||||||||||||||||||||||||||||||||||||||||||||||
13 | 10 Sqmm 2 Core | 100.00 | RM | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 1.02 | Construction of chamber for 100mm sluice plates | item2 | 213 | Nos | |||||||||||||||||||||||||||||||||||||||
14 | 16 Sqmm 4 core | 200.00 | RM | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 1.01 | Supplying, Conveying and fixing spls. Including eart | item1 | 123.223 | Nos | |||||||||||||||||||||||||||||||||||||||
15 | 25 Sqmm 3½ core | 200.00 | RM | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 1.02 | Construction of chamber for 100mm sluice plates | item2 | 213 | Nos | |||||||||||||||||||||||||||||||||||||||
16 | 50 Sqmm 3½ core | 130.00 | RM | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 2 | Construction of chamber for 100mm sluices valve | item3 | 10 | Nos | |||||||||||||||||||||||||||||||||||||||
17 | 95 Sqmm 3½ core | 130.00 | RM | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 1.02 | Construction of chamber for 100mm sluice plates | item2 | 213 | Nos | |||||||||||||||||||||||||||||||||||||||
18 | 120 Sqmm 3½ core | 100.00 | RM | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 2 | Construction of chamber for 100mm sluices valve | item3 | 10 | Nos | |||||||||||||||||||||||||||||||||||||||
19 | 150 Sqmm 3½ core | 100.00 | RM | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 1.02 | Construction of chamber for 100mm sluice plates | item2 | 213 | Nos | |||||||||||||||||||||||||||||||||||||||
20 | 185 Sqmm 3½ core | 100.00 | RM | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 2 | Construction of chamber for 100mm sluices valve | item3 | 10 | Nos | |||||||||||||||||||||||||||||||||||||||
21 | Supply & fixing in repair pin type porcelain, vitreous, white, brown or green insulators, including one galvanized mild steel spindle two galvanised iron washers and one galvanised iron nut, 100 mm height and 65mm dia suitable for working pressure upto and including 1100 volts grade for LT lines fixed on poles etc incl taking down old unsv Pin insulator complete all as specified and directed. | 3.00 | Each | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 1.02 | Construction of chamber for 100mm sluice plates | item2 | 213 | Nos | |||||||||||||||||||||||||||||||||||||||
22 | Supply and fixing in repair shackle type porcelain vitreous, white, brown or green insulator for working pressure 1100V of 115mm dia and 100mm high including galvanized mild steel strip 31 x 3mm, insulator bolts 14mm dia washer and nut for LT lines fixed on poles complete all as specified and directed. | 2.00 | Each | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 1.01 | Supplying, Conveying and fixing spls. Including eart | item1 | 123.223 | Nos | |||||||||||||||||||||||||||||||||||||||
23 | Supply & fixing in repair aluminium conductor, steel reinforced (ACSR) of any size/description on LT poles/lines including stringing, tightening, binding to insulators with aluminium wire making and connecting jumpers, connections etc including connecting, commissioning and testing ccomplete all as specified and directed. | 0.20 | Qtl | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 1.02 | Construction of chamber for 100mm sluice plates | item2 | 213 | Nos | |||||||||||||||||||||||||||||||||||||||
24 | Supplying and fixing in repair MCCB, 630 Amps, 4 pole, 415 Volts, AC supply, having breaking capacity Icu100% = 35/36 KA with adjustable thermal & magnetic setting, of complete all as specified and directed. Make : Legrand/Seimens/Schnieder/Havells/ C&S/Indoasian | 1.00 | Each Job | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 2 | Construction of chamber for 100mm sluices valve | item3 | 10 | Nos | |||||||||||||||||||||||||||||||||||||||
25 | Supplying and fixing in repair MCCB, 400 Amps, 4 pole, 415 Volts, AC supply, having breaking capacity Ics = 100% of Icu 35/36 kA with adjustable thermal & magnetic setting complete all as specified and directed. | 1.00 | Each Job | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 1.02 | Construction of chamber for 100mm sluice plates | item2 | 213 | Nos | |||||||||||||||||||||||||||||||||||||||
26 | Supplying and fixing in repair MCCB, 250 Amps, 4 pole, 415 Volts, AC supply, having breaking capacity Icu = 25 kA with adjustable thermal & magnetic setting, complete all as specified and directed. | 1.00 | Each Job | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 2 | Construction of chamber for 100mm sluices valve | item3 | 10 | Nos | |||||||||||||||||||||||||||||||||||||||
27 | Supplying and fixing in repair MCCB, 200 Amps, 4 pole, 415 Volts, AC supply, having breaking capacity Icu = 25 kA with adjustable thermal & magnetic setting,complete all as specified and directed. | 1.00 | Each Job | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 1.02 | Construction of chamber for 100mm sluice plates | item2 | 213 | Nos | |||||||||||||||||||||||||||||||||||||||
28 | Supplying and fixing in repair MCCB, 160 Amps, 3 pole, 415 Volts, AC supply, having breaking capacity Icu = 25 kA with fixed thermal & magnetic setting,complete all as specified and directed. | 1.00 | Each Job | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 2 | Construction of chamber for 100mm sluices valve | item3 | 10 | Nos | |||||||||||||||||||||||||||||||||||||||
29 | Supplying and fixing in repair MCCB, 100 Amps, 3 pole, 415 Volts, AC supply, having breaking capacity Icu = 25 kA with fixed thermal & magnetic setting, complete all as specified and directed. | 1.00 | Each Job | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 1.02 | Construction of chamber for 100mm sluice plates | item2 | 213 | Nos | |||||||||||||||||||||||||||||||||||||||
30 | Supplying and fixing MCCB, 63 Amps, 3 pole, 415 Volts, AC supply, having breaking capacity Icu = 25 kA with fixed thermal & magnetic setting, complete all as specified and directed. | 1.00 | Each Job | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 1.01 | Supplying, Conveying and fixing spls. Including eart | item1 | 123.223 | Nos | |||||||||||||||||||||||||||||||||||||||
31 | Disconnecting & taking down old existing unserviceable changeover switch of any description and in any position complete and Supplying, fixing, testing and commissioning of Euroload Load type changeover switch 4 pole, 415 volts, 320 Amps with and including sheet enclosure complete all as specified and directed. Cat part No: IHCNFEO320 of make Havells or equivalent model of specified make as approved by GE. | 1.00 | Each | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 1.02 | Construction of chamber for 100mm sluice plates | item2 | 213 | Nos | |||||||||||||||||||||||||||||||||||||||
32 | Disconnecting & taking down old existing unserviceable changeover switch of any description and in any position complete and Supplying, fixing, testing and commissioning of Euroload type changeover switch 4 pole, 415 volts, 200 Amps with and including sheet enclosure complete all as specified and directed. Cat part No: IHCNFE0200 of make Havells or equivalent model of specified make as approved by GE. | 1.00 | Each | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 2 | Construction of chamber for 100mm sluices valve | item3 | 10 | Nos | |||||||||||||||||||||||||||||||||||||||
33 | Disconnecting & taking down old existing unserviceable changeover switch of any description and in any position complete and Supplying, fixing, testing and commissioning of side operated OFF Load type changeover switch 4 pole, 415 volts, 200 Amps with and including sheet enclosure complete all as specified and directed. Cat part No: IHBFFE0200 of make Havells or equivalent model of specified make as approved by GE. | 1.00 | Each | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 1.02 | Construction of chamber for 100mm sluice plates | item2 | 213 | Nos | |||||||||||||||||||||||||||||||||||||||
34 | Disconnecting & taking down old existing unserviceable changeover switch of any description and in any position complete and Supplying, fixing, testing and commissioning of side operated ONLoad type changeover switch 4 pole, 415 volts, 100 Amps with and including sheet enclosure complete all as specified and directed. Cat part No: IHBFFE0100 of make Havells or equivalent model of specified make as approved by GE. | 1.00 | Each | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 2 | Construction of chamber for 100mm sluices valve | item3 | 10 | Nos | |||||||||||||||||||||||||||||||||||||||
35 | Disconnecting and Taking out old unserviceable LT Panel any type and shape, size, and Supply, installation, testing and commissioning Indoor door type factory made kisok cubicle type, dust and vermin proof of suitable size IP 54 class protection made of 3mm thick CRCA sheet and angle iron 50X50X6mm frame, TPN aluminium busbar of capacity 1500 Amp ,mounted in porcelin insulator duly drilled hole for cable connection including front and rear side opening with locking arrangement and provn for incoming and outgoing cables with glands including control wiring with minimum 1.5 sqmm PVC insulated copper conductor for measuring of voltage, amp with indicators RYB, painting with two coat of smoke grey synthetic enamelled paint over a coat of red oxide primer on PCC platform 100 mm thick made out of PCC 1:3:6, 1 mtrs all round the panel board suitable for 3 phase 4 wire 415 V, 50 Hz factory fabricated in an approved factory having modern fabrication and comprising of following :- (Location - Sub Stn No 2) | 1.00 | Each | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 2 | Construction of chamber for 100mm sluices valve | item3 | 10 | Nos | |||||||||||||||||||||||||||||||||||||||
36 | (i) Incoming :- (a)ACB , 1000 Amps, 4 pole, 415 Volts, AC supply, having breaking capacity , 50 KA drawout typed with microprocessor release IPR E , Qty – 01 Make:Legrand/Schnieder/Siemens/Havells) (b) Digital Ammeter 3 Phase AC 0 – 1000 Amps, with 3 current transformer of suitable ratio and capacity Qty -01 No. (c) Indicating lamps LED type for three phases -R Y B of 3 Nos, (d) Digital Voltmeter 3 Phase AC 0 – 500 Volts.Qty -01 No. (e) Aluminium bus-bar of 1500 Amps rating TPN -01 Set (ii) Out Going :- (a) MCCB, 315 Amps, 3 pole, 415 Volts, AC supply, having breaking capacity , 36 KA with adjustable thermal & fixed magnetic setting, Qty – 02 No.(Make: Legrand/Schneider/Siemens/Havells/C&S) (b) MCCB, 200 Amps, 3 pole, 415 Volts, AC supply, having breaking capacity , 25 KA with adjustable thermal & fixed magnetic setting, Qty – 5 No.(Make: Legrand/Schneider/Siemens/Havells/C&S) (c) MCCB, 100 Amps, 3 pole, 415 Volts, AC supply, having breaking capacity , 25 KA with adjustable thermal & fixed magnetic setting, Qty – 5 No.(Make: Legrand/Schneider/Siemens/Havells/C&S) (d) ON Load Change over sitch 630 A , 4 Pole 415 V Ac supply -01 No (Make: Legrand/Schneider/Siemens/Havells/C&S/L&T) | 1.02 | Construction of chamber for 100mm sluice plates | item2 | 213 | Nos | ||||||||||||||||||||||||||||||||||||||||||||||||
37 | Disconnecting and Taking out old unserviceable LT Panel any type and shape, size, and Supply, installation, testing and commissioning Indoor type factory made kisok cubicle type, dust and vermin proof of suitable size IP 54 class protection made of 3mm thick CRCA sheet and angle iron 50X50X6mm frame, TPN aluminium busbar of capacity 800 amps mounted in porcelin insulator duly drilled hole for cable connection including front and rear side opening with locking arrangement and provn for incoming and outgoing cables with glands including control wiring with minimum 1.5 sqmm PVC insulated copper conductor for measuring of voltage, amp with indicators RYB, painting with two coat of smoke grey synthetic enamelled paint over a coat of red oxide primer on PCC platform 100 mm thick made out of PCC 1:3:6, 1 mtrs all round the panel board suitable for 3 phase 4 wire 415 V, 50 Hz factory fabricated in an approved factory having modern fabrication and comprising of following :- (Location - Sub Stn No 2) | 1.00 | Each Job | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 2 | Construction of chamber for 100mm sluices valve | item3 | 10 | Nos | |||||||||||||||||||||||||||||||||||||||
38 | (i) Incoming :- (a)ACB , 630 Amps, 4 pole, 415 Volts, AC supply, having breaking capacity , 50 KA drawout typed with microprocessor release IPR E , Qty – 01 Make:Legrand/Schnieder/Siemens/Havells) (b) Digital Ammeter 3 Phase AC 0 – 1000 Amps, with 3 current transformer of suitable ratio and capacity Qty -01 No. (c) Indicating lamps LED type for three phases -R Y B of 3 Nos, (d) Digital Voltmeter 3 Phase AC 0 – 500 Volts.Qty -01 No. (e) Aluminium bus-bar of 800 Amps rating TPN -01 Set (ii) Out Going :- (a) MCCB, 315 Amps, 3 pole, 415 Volts, AC supply, having breaking capacity , 35 KA with adjustable thermal & fixed magnetic setting, Qty – 02 No.(Make: Legrand/Schneider/Siemens/Havells/C&S) a) MCCB, 250 Amps, 3 pole, 415 Volts, AC supply, having breaking capacity , 25 KA with adjustable thermal & fixed magnetic setting, Qty – 02 No.(Make: Legrand/Schneider/Siemens/Havells/C&S) (c) MCCB, 100 Amps, 3 pole, 415 Volts, AC supply, having breaking capacity , 55 KA with adjustable thermal & fixed magnetic setting, Qty – 6 No.(Make: Legrand/Schneider/Siemens/Havells/C&S) | 1.02 | Construction of chamber for 100mm sluice plates | item2 | 213 | Nos | ||||||||||||||||||||||||||||||||||||||||||||||||
39 | Disconnecting and Taking out old unserviceable LT Panel any type and shape, size, and Supply, installation, testing and commissioning out door type factory made kisok cubicle type, dust and vermin proof of suitable size IP 65 class protection made of 3mm thick CRCA sheet and angle iron 50X50X6mm frame, TPN aluminium busbar of capacity 600 amps mounted in porcelin insulator duly drilled hole for cable connection including front and rear side opening with locking arrangement and provn for incoming and outgoing cables with glands including control wiring with minimum 1.5 sqmm PVC insulated copper conductor for measuring of voltage, amp with indicators RYB, painting with two coat of smoke grey synthetic enamelled paint over a coat of red oxide primer on PCC platform 100 mm thick made out of PCC 1:3:6, 1 mtrs all round the panel board suitable for 3 phase 4 wire 415 V, 50 Hz factory fabricated in an approved factory having modern fabrication and comprising of following :- (Location -PRC) (i) Incoming :- (a) MCCB, 400 Amps, 4 pole, 415 Volts, AC supply,Havinf breaking Capacity 36 KA with adjustable thermal & fixed magnetic setting Qty – 01 Make:Legrand/Schnieder/Siemens/Havells) (b) Digital Ammeter 3 Phase AC 0 – 500 Amps, with 3 current transformer of suitable ratio and capacity Qty -01 No. (c) Indicating lamps LED type for three phases -R Y B of 3 Nos, (d) Digital Voltmeter 3 Phase AC 0 – 500 Volts.Qty -01 No. (e) Aluminium bus-bar of 600 Amps rating TPN - 01 set (ii) Out Going :- (a) MCCB, 250 Amps, 3 pole, 415 Volts, AC supply, having breaking capacity , 25 KA with adjustable thermal & fixed magnetic setting, Qty –1 No. (Make: Legrand/Schneider/Siemens/Havells/L&T) (b) MCCB, 200 Amps, 3 pole, 415 Volts, AC supply, having breaking capacity , 25 KA with adjustable thermal & fixed magnetic setting, Qty –1 No. (Make: Legrand/Schneider/Siemens/Havells/L&T) (c) MCCB, 100 Amps, 3 pole, 415 Volts, AC supply, having breaking capacity , 25 KA with adjustable thermal & fixed magnetic setting, Qty – 02. (Make: Legrand/Schneider/Siemens/Havells/L&T Note : (i) The contractor shall submit proposed drawing of the panel interlia mentioning make of switchgears to be incorporated alongwith name of panel manufacturer for approval of GE before manufacturing. (ii) The quoted rate is inclusive of the cost of danger notice plate of suitable size and marking of letters with PVC sheet/ Stickers such as incoming and outgoing and capacity of breakers etc. (iv) The cost of fixing of the panel on suitable PCC (1:3:6) type C-1(using 20 mm graded black trap/basalt/granite stone aggregates) foundation as directed by Engineer-in-Charge is deemed to be included in the quoted rates by the contractor for the above item. (v) The bottom of panel shall have minimum 45cm height from existing ground / floor level. | 1.00 | Each Job | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 1.01 | Supplying, Conveying and fixing spls. Including eart | item1 | 123.223 | Nos | |||||||||||||||||||||||||||||||||||||||
40 | Dismantling, taking down and removing the old existing un serviceable non-functional/broken GI sheet/hinges of any description and in any position of existing feeder pillar boxes/panel boards/feeder pillar boxes etc and supplying and fixing GI sheet 3.00 mm thick including hings for door of panel/main switch etc with necessary spot welding etc including making necessary adjustment for free and smooth movement of panel and locking arrangements complete all as specified and directed by Engineer-in-Charge. | 70.00 | Kg | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 1.02 | Construction of chamber for 100mm sluice plates | item2 | 213 | Nos | |||||||||||||||||||||||||||||||||||||||
41 | M & L for preparation of old painted steel surface by cleaning, removing rust, grease and apply one coat of synthetic enamel paint of approved shade (Spray painting outside/inside surface) of the feeder pillar box / LT Panels Outdoor / Indoor type of any size and type complete with prior permission of Engineer in Charge. Base frame with Black enamel paint (Rate quoted shall deem to be included of Numbering of Panel/ Feeder pillar) complete all as specified and directed by Engineer charge | 15.00 | Sqm | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 1.02 | Construction of chamber for 100mm sluice plates | item2 | 213 | Nos | |||||||||||||||||||||||||||||||||||||||
42 | M & L for servicing of feeder pillar box, after dismantling the incoming and outgoing connections from MCCB/ Bus bar and replacing the old burnt/ overheated unserviceable lugs, terminals, nuts, bolts, washers supporting insulators etc and checking the serviceability of MCB / MCCB, earth continuity conductor and strip etc complete all as specified and directed by Engineer-in-Charge. Note: (i) Spare parts such as terminals, lugs, nut bolts, insulators etc will be measured and paid under respective item in the schedule, (ii) Labour for fixing charges of the spare parts deemed to be included in the rate quoted for the items. | 6.00 | Each Job | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 2 | Construction of chamber for 100mm sluices valve | item3 | 10 | Nos | |||||||||||||||||||||||||||||||||||||||
43 | Supply only aluminium lugs of any type / shape of capacity 150 Sqmm | 15.00 | Each | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 1.02 | Construction of chamber for 100mm sluice plates | item2 | 213 | Nos | |||||||||||||||||||||||||||||||||||||||
44 | Supply only aluminium lugs of any type / shape of capacity 120 Sqmm | 15.00 | Each | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 2 | Construction of chamber for 100mm sluices valve | item3 | 10 | Nos | |||||||||||||||||||||||||||||||||||||||
45 | Supply only aluminium lugs of any type / shape of capacity 95 Sqmm | 15.00 | Each | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 1.02 | Construction of chamber for 100mm sluice plates | item2 | 213 | Nos | |||||||||||||||||||||||||||||||||||||||
46 | Supply only aluminium lugs of any type / shape of capacity 70 Sqmm | 20.00 | Each | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 1.01 | Supplying, Conveying and fixing spls. Including eart | item1 | 123.223 | Nos | |||||||||||||||||||||||||||||||||||||||
47 | Supply only aluminium lugs of any type / shape of capacity 50 Sqmm | 20.00 | Each | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 1.02 | Construction of chamber for 100mm sluice plates | item2 | 213 | Nos | |||||||||||||||||||||||||||||||||||||||
48 | Supply only aluminium lugs of any type / shape of capacity 35 Sqmm | 20.00 | Each | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 2 | Construction of chamber for 100mm sluices valve | item3 | 10 | Nos | |||||||||||||||||||||||||||||||||||||||
49 | Supply only aluminium lugs of any type / shape of capacity 25 Sqmm | 25.00 | Each | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 1.02 | Construction of chamber for 100mm sluice plates | item2 | 213 | Nos | |||||||||||||||||||||||||||||||||||||||
50 | Supply only aluminium lugs of any type / shape of capacity 16 Sqmm | 25.00 | Each | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 2 | Construction of chamber for 100mm sluices valve | item3 | 10 | Nos | |||||||||||||||||||||||||||||||||||||||
51 | Supply only GI Nuts, bolts, screws, washers of required sizes | 10.00 | KG | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 1.02 | Construction of chamber for 100mm sluice plates | item2 | 213 | Nos | |||||||||||||||||||||||||||||||||||||||
52 | Supply only bus bar Insulators Epoxy type as required at site min size 45mm x 50 mm dia | 12.00 | Each | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 2 | Construction of chamber for 100mm sluices valve | item3 | 10 | Nos | |||||||||||||||||||||||||||||||||||||||
53 | S&F in repair Extension link four set suitable for MCCB in existing panel of capacity DPX 125/160 Amp. | 5.00 | Each SET | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 1.02 | Construction of chamber for 100mm sluice plates | item2 | 213 | Nos | |||||||||||||||||||||||||||||||||||||||
54 | S&F in repair Extension link four set suitable for MCCB in existing panel of capacity DPX 250 Amp. | 3.00 | Each SET | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 1.01 | Supplying, Conveying and fixing spls. Including eart | item1 | 123.223 | Nos | |||||||||||||||||||||||||||||||||||||||
55 | S&F in repair Extension link four set suitable for MCCB in existing panel of capacity DPX 400/600 Amp. | 2.00 | Each SET | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 1.02 | Construction of chamber for 100mm sluice plates | item2 | 213 | Nos | |||||||||||||||||||||||||||||||||||||||
56 | Taking down unserviceable indication lamp and supplying, fixing, testing and commissioning indication lamp (LED type) with showing red, yellow and green in colour of 22.5 mm dia monitor on LT panel board suitable for 240 V AC supply all as specified and directed. Make : L&T /Binay.or equivalent approved. | 3.00 | Each Set of 3 | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 2 | Construction of chamber for 100mm sluices valve | item3 | 10 | Nos | |||||||||||||||||||||||||||||||||||||||
57 | Disconnecting, dismantling, taking out & removing unserviceable volt meter and Supplying, fixing, testing and commissioning of digital electronic volt meter 0-500 V range suitable for LT 415 Volts panel flush pattern square type 96mmX96mm with adopter complete with button all as specified and directed. Make : ENERCON/AE Note :- The rate quoted shall be deemed to including the following:- (i) Control wiring for auxiliary supply 230 Volts AC if required. (ii) Cutting the sheet of the panel to suit with existing panel if required. (iii) Calibration and testing the meter. | 5.00 | Each | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 1.02 | Construction of chamber for 100mm sluice plates | item2 | 213 | Nos | |||||||||||||||||||||||||||||||||||||||
58 | Disconnecting, dismantling, taking out & removing unserviceable Amp meter Supplying, fixing, testing and commissioning of digital electronic ammeter double ratio with 5 Amps secondary current of any range flush pattern sequence type 96mmX96mm with adopter suitable for existing CT ratio for maintaining on LT 415 Volts panel complete built in selector switch including taking the old unserviceable Ammeter complete all as specified and directed. Make : ENERCON/AE. Note :- The rate quoted shall be deemed to including the following :- (i) Control wiring for auxiliary supply 230 Volts AC if required. (ii) Cutting the sheet of the panel to suit with existing panel if required. (iii) Calibration and testing the meter. | 5.00 | Each | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 2 | Construction of chamber for 100mm sluices valve | item3 | 10 | Nos | |||||||||||||||||||||||||||||||||||||||
59 | Demolition of cement concrete (unreinforced) of any description as in ground floors and pavings not exceeding 15 cm thickness (above or below ground floors) complete all as specified and directed. | 1.00 | Cum | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 1.02 | Construction of chamber for 100mm sluice plates | item2 | 213 | Nos | |||||||||||||||||||||||||||||||||||||||
60 | M&L for cement concrete 1:3:6 type C-1 (using 20 mm graded crushed stone aggregate) as in cills, steps, copings, holdfast and the like including weathering, slightly rounded or chamfered angles and throating as directed with and including necessary form work complete all as specified and directed. | 1.00 | Cum | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 2 | Construction of chamber for 100mm sluices valve | item3 | 10 | Nos | |||||||||||||||||||||||||||||||||||||||
61 | Supplying, Fixing, jointing and testing for provision of Heat Shrinkable outdoor straight through joints,complete with jointing materials and accessories , suitable for XLPE, LT Cable, 1100 Volts grade, for the following sizes of cables complete all as specified and directed. | 1.02 | Construction of chamber for 100mm sluice plates | item2 | 213 | Nos | ||||||||||||||||||||||||||||||||||||||||||||||||
62 | 25 Sqmm to 50 sqmm 3½ core | 2.00 | Each Job | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 1.01 | Supplying, Conveying and fixing spls. Including eart | item1 | 123.223 | Nos | |||||||||||||||||||||||||||||||||||||||
63 | 70 Sqmmto 150 sqmm 3½ core | 2.00 | Each Job | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 1.02 | Construction of chamber for 100mm sluice plates | item2 | 213 | Nos | |||||||||||||||||||||||||||||||||||||||
64 | 185 Sqmmto 240 sqmm 3½ core | 2.00 | Each Job | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 2 | Construction of chamber for 100mm sluices valve | item3 | 10 | Nos | |||||||||||||||||||||||||||||||||||||||
65 | Supplying, Fixing, jointing and testing for provision of Heat Shrinkable Outdoor termination cable jointing kit , suitable for XLPE, LT Cable, 1100 Volts grade, for the following sizes of cables complete all as specified and directed.. | 1.02 | Construction of chamber for 100mm sluice plates | item2 | 213 | Nos | ||||||||||||||||||||||||||||||||||||||||||||||||
66 | 25 Sqmm to 50 sqmm 3½ core | 2.00 | Each Job | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 2 | Construction of chamber for 100mm sluices valve | item3 | 10 | Nos | |||||||||||||||||||||||||||||||||||||||
67 | 70 Sqmm to 150 sqmm 3½ core | 2.00 | Each Job | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 1.02 | Construction of chamber for 100mm sluice plates | item2 | 213 | Nos | |||||||||||||||||||||||||||||||||||||||
68 | 185 Sqmm to 300 sqmm 3½ core | 2.00 | Each Job | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 2 | Construction of chamber for 100mm sluices valve | item3 | 10 | Nos | |||||||||||||||||||||||||||||||||||||||
69 | Material and labour for earthing complete with galvanized steel earth plate electrode 600mm X 600mm X 6mm buried directly in ground vertically to a depth not less than 2.25 meter below normal ground level (with top edge of earth plate not less than 1.5 meter below ground level) connected to galvanized iron earth lead 32X 6 mm GI strip, (main earthing lead ) by means of galvanized bolts, nuts and washers all as shown in electrical plate No .3 of MES Schedule Part-I (2020) with connected to earth test point & to main switch board with & including adequate quantity of charcoal dust and common salt alround earth plate & 40 mm dia GI pipe light grade for earth lead protection pipe for suitable length and GI pipe 20 mm dia light grade for watering pipe with funnel & wire mesh incl necessary excavation and earth work in any type of soil, and PCC (1: 3 : 6) type C-1 (using 20 mm graded black trap/ granite/ Basalt stone aggregate) for earth pit with 40x40x6 mm mild steel angle iron frame for cover and 40 mm thick precast RCC cover in 1 : 2 : 4 type B1(using 20 mm graded black trap/granite/ basalt stone aggregate) with 3 Nos 8 mm dia TMT bars both ways with 12mm dia round bar handle, complete all as specified & directed . NOTE : RCC pit cover shall be pre-cast of RCC (1:2;4) type B-1 80 mm thick reinforced with XPM weighting not less than 4 Kgs/Sqm in lieu of CI cover. | 6.00 | Each | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 1.02 | Construction of chamber for 100mm sluice plates | item2 | 213 | Nos | |||||||||||||||||||||||||||||||||||||||
70 | Material and labour in replacement of UNSV GI strip of size 32mm x 6mm for laying along the wall/roof on batten or burried in ground or drawn in conduit pipe or fixed to poles or any other situation as directed or as required GI strip of size 32mm x 6mm earth continuity conductor complete with all accessories such as porcelain insulators, saddles and fixing screw etc for conductor acomplete all as specified and directed. | 30.00 | RM | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 1.01 | Supplying, Conveying and fixing spls. Including eart | item1 | 123.223 | Nos | |||||||||||||||||||||||||||||||||||||||
71 | All as per item No.70 here in above but using 4 mm dia galvanised iron or steel wire complete all as specified and directed. | 25.00 | RM | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 1.02 | Construction of chamber for 100mm sluice plates | item2 | 213 | Nos | |||||||||||||||||||||||||||||||||||||||
72 | Disconnecting, dismantling, taking out & removing unserviceable MCCB box and Supplying and fixing of Single door Mild steel MCCB Enclosure box suitable for provn of MCCB range 200 amp to 400 amp capacity complete all as specified and directed. | 2.00 | Each | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 1.01 | Supplying, Conveying and fixing spls. Including eart | item1 | 123.223 | Nos | |||||||||||||||||||||||||||||||||||||||
73 | Disconnecting and taking out old unserviceable GI pipe and Supplying, laying & jointing GI water tubing, 50 mm bore, light grade as in sleeving etc laid in trenches / pole post etc, cutting and making necessaries arangement by means of wedling and jointing suitable for post of larntent/ street light fitting including PCC work complete all as specified and directed . | 24.00 | RM | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 1.02 | Construction of chamber for 100mm sluice plates | item2 | 213 | Nos | |||||||||||||||||||||||||||||||||||||||
74 | Labour only for checking the serviceability of the different spares / components / parts of LED security light fittings/post top lantern light fittings ,LED flood light fittings etc, any wattage/capacity) of any description and fixed in any position, replacement of un-serviceable/damaged/ broken part(s) either in single or in combination, re-assembling the fittings and making the light fittings serviceable, fixing the fittings in position, connecting to electric supply and its testing on installation complete all as specified and directed here in after in notes NOTES FOR SCH `A’ ITEM NO 74:- (i) Replacement of parts i.e Drivers,SPD, LED board,lamps, choke, Igniter, Condenser, Holder, covers etc for Street/Flood light fittings any wattage & capacity, if any required at site, shall be measured and paid for separately under appropriate item of Schedule `A' as ‘supply only. (ii) Necessary T&P i.e. ladder, tools etc required for checking and making the light fittings in serviceable conditions, its fixing in position and testing shall be arranged by the contractor at his own cost for checking and fixing of street light fittings/security light fittings of any description on poles / on walls / on pillars etc i.e. in any position at site. (iii) Required screws, insulating tapes, internal wiring wire and other minor items excluding the required spares parts for repairing and making the street light fittings/security light fittings in serviceable condition, will be arranged & supplied by the contractor and cost of which is deemed to be included in the rates quoted by the contractor in above respective item. (iv) Contractor shall be paid only one time the labour charges quoted above in Schedule `A' items for a particular fitting repaired irrespective of the number of times labour and resources arranged by him to check the serviceability of the fittings and replacement of unserviceable / defective parts in order to maintain the fittings in serviceable/working condition. (v) Contractor’s quoted rates for Schedule `A' item No 74 is deemed to include for inspection/checking the serviceability of the fittings in position or by taking down as per site requirement, removing the damaged unserviceable / broken parts, fixing the new parts as required, fixing the fittings in same position or the other, connecting the fittings with electric source and testing of fittings as directed. | 100.00 | Each Job | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 1.02 | Construction of chamber for 100mm sluice plates | item2 | 213 | Nos | |||||||||||||||||||||||||||||||||||||||
75 | Supply only the following parts for LED fittings complete all as specified and directed. NOTES: (i) Fixing element of these items is deemed to be included in the rates quoted by the contractor for Sch `A' item No 74 (ii) Spare parts/items shall be of make Crompton Greaves/Philips/Bajaj/Havells & suitable for the existing fittings. (iii) The above items shall be operated with prior written approval of GE and when required spares are not available with the deptt to issue to contractor under Sch ‘B’ “Free for fixing” and Contractor shall have no claim on account of non execution of above items. | 2 | Construction of chamber for 100mm sluices valve | item3 | 10 | Nos | ||||||||||||||||||||||||||||||||||||||||||||||||
76 | Driver Suitable for 45/48Watt LED fittings. Make:C&S/Havells/Bajaj/Crompton | 5.00 | Each | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 1.02 | Construction of chamber for 100mm sluice plates | item2 | 213 | Nos | |||||||||||||||||||||||||||||||||||||||
77 | Driver Suitable for 60Watt LED fittings, Make:C&S/Havells/Bajaj/Crompton | 10.00 | Each | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 1.01 | Supplying, Conveying and fixing spls. Including eart | item1 | 123.223 | Nos | |||||||||||||||||||||||||||||||||||||||
78 | Driver Suitable for 90Watt LED fittings, Make:C&S/Havells/Bajaj/Crompton | 10.00 | Each | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 1.02 | Construction of chamber for 100mm sluice plates | item2 | 213 | Nos | |||||||||||||||||||||||||||||||||||||||
79 | Driver Suitable for 100/120/150Watt LED fittings. Make:C&S/Havells/Bajaj/Crompton | 10.00 | Each | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 2 | Construction of chamber for 100mm sluices valve | item3 | 10 | Nos | |||||||||||||||||||||||||||||||||||||||
80 | Driver Suitable for 100/120/150Watt LED fittings. Make:C&S/Havells/Bajaj/Crompton | 10.00 | Each | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 2 | Construction of chamber for 100mm sluices valve | item3 | 10 | Nos | |||||||||||||||||||||||||||||||||||||||
81 | M&L for making holes in electric/street light poles of any height or in any shape, by means of drill machine and drawing of drawing of 1.5sqmm x3 core cable through the hole from junction box to the hole on the top of pole near the street light fitting complete with all electric connections complete all as specified and directed. (Rates of the cable deemed to be included) | 25.00 | Each | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 2 | Construction of chamber for 100mm sluices valve | item3 | 10 | Nos | |||||||||||||||||||||||||||||||||||||||
82 | Taking down existing unserviceable bracket complete and S&F 40 mm dia GI light grade pipe bracket 1.50 m long bent to shape by cutting & welding as required & directed and fixed to pole with two Nos of FI clamps 40x5 mm to be tightened with bolts, nut and washers and including painted with two coat of aluminium paint over a coat of red oxide primer complete all as specified and directed. Make of pipe TATA / Jindal / Swastik / Prakash / BST or any other ISI marked make approved by GE. | 6.00 | Each | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 2 | Construction of chamber for 100mm sluices valve | item3 | 10 | Nos | |||||||||||||||||||||||||||||||||||||||
83 | Supply and fixing in replacement of UNSV LED bollard light 10 W, IP 65 rated ,efficient light distribution complete with accessories to be fixed in Ground including connecting the fitting to control switch at the bottom of the Junction box with using 2.5 Sqmm two single core PVC insulated and unsheathed copper conductor cable complete,all as specified and directed Make : Crompton/ Havells/ C&S/Bajaj (Note :PCC work shall be measured and paid seperatly under Sch "A' relevent item and rate of cable deemed to be included ) | 6.00 | Each | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 1.01 | Supplying, Conveying and fixing spls. Including eart | item1 | 123.223 | Nos | |||||||||||||||||||||||||||||||||||||||
84 | Supply and fixing in replacement of UNSV 20W LED Post top lantern complete accessories to be fixed on pole/wall including connecting the fitting to control switch at the bottom of the pole with using 2.5 Sqmm two single core PVC insulated and unsheathed copper conductor cable complete,all as directed and directed. Make : Cromptonof /Havells/ C&S/Bajaj/Shakti. (Note :PCC work shall be measured and paid seperatly under Sch "A' relevent item and rate of cable deemed to be included ) | 6.00 | Each | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 1.02 | Construction of chamber for 100mm sluice plates | item2 | 213 | Nos | |||||||||||||||||||||||||||||||||||||||
85 | Supply and fixing in replacement of UNSV 40W LED Post top lantern complete accessories to be fixed on pole/wall including connecting the fitting to control switch at the bottom of the pole with using 2.5 Sqmm two single core PVC insulated and unsheathed copper conductor cable complete,all as directed and directed. Make : Crompton/ Havells/ C&S/Bajaj/ Shakti. (Note :PCC work shall be measured and paid seperatly under Sch "A' relevent item and rate of cable deemed to be included ) | 4.00 | Each | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 1.02 | Construction of chamber for 100mm sluice plates | item2 | 213 | Nos | |||||||||||||||||||||||||||||||||||||||
86 | Taking down old unserviceable junction boxes from the pole with disconnectiong all connections, Supplying and fixing in position Junction box made of SMC/FRP sheet ready made of size 300 mm x 200 x 105 mm having 100 A Capacity RYB and neutral aluminium bus bar of 3 mm thick duly fitted on suitable insulator . The gasket should be internally embedded, and made of Polyeutherene. Box shall be suitable for up to 35 Sqmm cables including one no. MCB SP 230 volts 6 amps and connecting the bus bars to cables with using suitable GI nut, bolts and washers and aluminum lugs etc fixed on pole using 30x5mm FI clamps,nuts,bolts & washers complete all as specified and directed. | 15.00 | Each | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 2 | Construction of chamber for 100mm sluices valve | item3 | 10 | Nos | |||||||||||||||||||||||||||||||||||||||
87 | All as per item No 88 above but Junction Box size 205 X 255 X112 MM (LXBXH) and shall be suitable for 16/25Sqmm cables . | 20.00 | Each | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 1.02 | Construction of chamber for 100mm sluice plates | item2 | 213 | Nos | |||||||||||||||||||||||||||||||||||||||
88 | Material & labour of PCC 1:3:6 type C-2 using 20 mm graded stone aggregate (4 stay). in mass concrete and filling complete for foundation/hard standing coping , complete all as specified and directed. | 1.00 | Cum | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 1.01 | Supplying, Conveying and fixing spls. Including eart | item1 | 123.223 | Nos | |||||||||||||||||||||||||||||||||||||||
89 | M&L for PCC 1:4:8 type D-2 (using 40mm graded crushed stone aggregate) as in foundation filling of poles and mass concrete etc complete all as specified and directed. | 0.50 | Cum | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 1.01 | Supplying, Conveying and fixing spls. Including eart | item1 | 123.223 | Nos | |||||||||||||||||||||||||||||||||||||||
90 | M & L for cutting chases in hard standing road/path/drain etc for passing cables/pipes etc. size of and removing the excavated materials and disposal at 50 metre distance and making good the cutting after the pipe and cables are laid with PCC 1:3:6 type C-1 using 20mm graded stone aggregates complete all as specified and directed. | 0.50 | Cum | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 1.02 | Construction of chamber for 100mm sluice plates | item2 | 213 | Nos | |||||||||||||||||||||||||||||||||||||||
91 | Supplying,erecting and fixing in replacement of UNSV steel tubular swaged pole (410 SP – 31), 9 mtr long,in true vertical position complete conforming to IS : 2713 (Part-I & III) 1980 with cast iron base plate, pole cap / finial taper plug, bolts, nuts and washers, welded reduced section and longitudinal weld throughout entire length of pole with and including 2 coats of black bituminous paint externally upto planting depth and remaining exterior portion of pole finished with one coat of red oxide primer complete, all as specified and directed. (Note : Excavation and PCC work shall be measured and paid seperatly under Sch "A' relevent item) | 2.00 | Each | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 1.02 | Construction of chamber for 100mm sluice plates | item2 | 213 | Nos | |||||||||||||||||||||||||||||||||||||||
92 | Supply, fixing & testing in replacement of UNSV 45W LED street light IP66 Powder coated pressure die cast aluminium High power LED street light with heat resistant toughened glass with lens, complete with all accessories duly prewired and suitable fixing arragement for mounting on existing MS frame bracket including connecting the fitting complete all as specified and directed. Make- Crompton / Havells/C& S/Bajaj / Shakti. (Note :- GI pipe bracket and clamp shall be measured and paid seperatly under Sch "A' relevent item) | 5.00 | Each Job | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 1.02 | Construction of chamber for 100mm sluice plates | item2 | 213 | Nos | |||||||||||||||||||||||||||||||||||||||
93 | Supply, fixing & testing in replacement of UNSV 60W LED street light IP66 Powder coated pressure die cast aluminium High power LED street light with heat resistant toughened glass with lens, complete with all accessories duly prewired and suitable fixing arragement for mounting on existing MS frame bracket including connecting the fitting complete all as specified and directed. Make- Crompton / Havells/C& S/Bajaj). (Note :- GI pipe bracket and clamp shall be measured and paid seperatly under Sch "A' relevent item) | 5.00 | Each Job | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 2 | Construction of chamber for 100mm sluices valve | item3 | 10 | Nos | |||||||||||||||||||||||||||||||||||||||
94 | Supply, fixing & testing in replacement of UNSV 70W LED street light IP66 Powder coated pressure die cast aluminium High power LED street light with heat resistant toughened glass with lens, complete with all accessories duly prewired and suitable fixing arragement for mounting on existing MS frame bracket including connecting the fitting complete all as specified and directed. Make- Crompton/Havells/C& S/Bajaj/ Shakti. (Note :- GI pipe bracket and clamp shall be measured and paid seperatly under Sch "A' relevent item) | 15.00 | Each Job | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 2 | Construction of chamber for 100mm sluices valve | item3 | 10 | Nos | |||||||||||||||||||||||||||||||||||||||
95 | Supply, fixing & testing in replacement of UNSV 90W LED street light IP66 Powder coated pressure die cast aluminium High power LED street light with heat resistant toughened glass with lens, complete with all accessories duly prewired and suitable fixing arragement for mounting on existing MS frame bracket including connecting the fitting complete all as specified and directed. Make- Crompton/Havells/C& S/Bajaj/ Shakti. (Note :- GI pipe bracket and clamp shall be measured and paid seperatly under Sch "A' relevent item) | 15.00 | Each Job | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 1.01 | Supplying, Conveying and fixing spls. Including eart | item1 | 123.223 | Nos | |||||||||||||||||||||||||||||||||||||||
96 | Supply, fixing & testing in replacement of UNSV 120W LED Flood light IP66 Powder coated pressure die cast aluminium High power LED street light with heat resistant toughened glass with lens, complete with all accessories duly prewired and suitable fixing arragement for mounting on existing 16 mtrs High Mast/11 mtrs pole /9 mtrs poleor Bldg MS frame/ bracket including connecting the fitting complete all as specified and directed. Make- Crompton/Havells/C& S/Bajaj/Shakti (Note : GI pipe bracket shall be measured and paid seperatly under Sch "A' relevent item) | 10.00 | Each Job | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 1.02 | Construction of chamber for 100mm sluice plates | item2 | 213 | Nos | |||||||||||||||||||||||||||||||||||||||
97 | Material and labour for cleaning and preparation of all existing steel surfaces of straight Electric/ steel tubular poles 9 mtrs long for painting including mild steel cross arms, clamps and street light brackets,protection pipe, MS boxes etc and applying Two coat of aluminium paint all round the exposed steel surfaces of existing steel tubular poles of any description and in any position above the height of 1.50 mtr from the plinth of the pole and applying one coat of synthetic enameled paint of different colours in strips of 150mm width upto the height 1.5 mtr from the plinth of pole complete all as specified and directed. | 20.00 | Each Job | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 2 | Construction of chamber for 100mm sluices valve | item3 | 10 | Nos | |||||||||||||||||||||||||||||||||||||||
98 | M & L for re-writing letters or figures (Black, roman, Indian) for electric/ street light pole Nos on existing poles with stencil out with black colour including fixing red colour radium of 80 mm hight arround the radius of pole complete all as specified and directed. | 25.00 | Each Job | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 1.02 | Construction of chamber for 100mm sluice plates | item2 | 213 | Nos | |||||||||||||||||||||||||||||||||||||||
99 | Supply and fixing in replacement of automatic street light switch using Nature Switch for automatic switching of street light based on LUX level of nature light having ON ≤ 30 lux and OFF ≥ 10 Lux . The sensor (Nature Switch) along with suitable power contactor , MCB and support termianl should be enclosure made of rust proof, electric shock proof , termite proof and FR grade SMC junction box(sintex make) conforming to confirmining IS 13947.4-1 & IS 8828, IP 66 including contactors ( 3 Nos each) and incoming- ourgoing MCBs ( 3 Nos each) rating of 16 amp and Circuit copper wiring of min 25 Sqmm cable incl taking down complete all as specified and directed. Make: Swadeep -02EC5kW3P , or Equivalent to Indoasian /Legrand | 2.00 | Each | Excess(+) | 1 | Full Conversion | INR | 0.00 | 0.00 | INR Zero Only | 1.01 | Supplying, Conveying and fixing spls. Including eart | item1 | 123.223 | Nos | |||||||||||||||||||||||||||||||||||||||
Total in Figures | 0.00 | 0.00 | ||||||||||||||||||||||||||||||||||||||||||||||||||||
Quoted Rate in Figures | Select | 0.0000 | 0.0000 | Zero Only | ||||||||||||||||||||||||||||||||||||||||||||||||||
Quoted Rate in Words | INR Zero Only |
Andaman & Nicobar Tenders |Andhra Pradesh Tenders |Arunachal Pradesh Tenders |Assam Tenders |Bihar Tenders |Chandigarh Tenders |Chhattisgarh Tenders |Dadra & Nagar Haveli Tenders |Daman & Diu Tenders |Delhi Tenders |Goa Tenders |Gujarat Tenders |Haryana Tenders |Himachal Pradesh Tenders |Jammu & Kashmir Tenders |Jharkhand Tenders |Karnataka Tenders |Kerala Tenders |Ladakh Tenders |Lakshadweep Tenders |Madhya Pradesh Tenders |Maharashtra Tenders |Manipur Tenders |Meghalaya Tenders |Mizoram Tenders |Nagaland Tenders |Odisha Tenders |Pondicherry Tenders |Punjab Tenders |Rajasthan Tenders |Sikkim Tenders |Tamil Nadu Tenders |Telangana Tenders |Tripura Tenders |Uttarakhand Tenders |Uttar Pradesh Tenders |West Bengal Tenders |