Bidhelp
E-IN-C BRANCH - MILITARY ENGINEER SERVICES||CE EC AND CE SHILLONG ZONE - MES||CWE HQ 137 WE - MES||GE SILCHAR - MES
E-IN-C BRANCH - MILITARY ENGINEER SERVICES||CE EC AND CE SHILLONG ZONE - MES||CWE HQ 137 WE - MES||GE SILCHAR - MES
GE
Assam QTY :

Items - REPAIRS MAINTENANCE OF LT PANELS LT FEEDER PILLAR BOX ETC FOR IMPROVEMENT OF DIFFERENT ELECT SUPPLY INSTALLATION INCL MISC WK SERVICES IN NCC ARO KUMBHIGRAM AND MASIMPUR UNDER GE SILCHAR

Tender Details
Costs
Documents
BOQ

BoQ1

Item Rate BoQ
BoQ_Ver3.0Item RateNormalINR OnlyINR
Select, Excess (+), Less (-)Less (-)
Tender Inviting Authority: GE SILCHAR
Name of Work:REPAIRS/ MAINTENANCE OF LT PANELS, LT FEEDER PILLAR BOX ETC FOR IMPROVEMENT OF DIFFERENT ELECT SUPPLY INSTALLATION INCL MISC WK SERVICES IN NCC/ ARO, KUMBHIGRAM & MASIMPUR UNDER GE SILCHAR
Contract No: CA NO: GE/SIL/ of 2025-26
Name of the Bidder/ Bidding Firm / Company :
PRICE SCHEDULE (This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only )
Sl. No.Item DescriptionItem Code / MakeQuantityUnitsEstimated Rate in Rs. PAddition / DeductionAddition / Deduction ValuesCurrency Convertion against each ItemQuoted Currency in INR / Other CurrencyRATE In Figures To be entered by the Bidder Rs. P Excise DutyVATFreight Charges ( Unloading & Stacking)Any Other Taxes/Duties/LeviesOther Taxes 2IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service TaxLess for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT in Rs. PTOTAL AMOUNT (Rs) TOTAL AMOUNT In Words
12334678910111251415161718192021222324252627282930313233343536373839404142434445464748495051525367
1.00Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth for foundations, manholes, etc. or for laying cables/pipes, erecting poles, etc. not exceeding 10sqm on plan and getting out in soft / loose soil complete all as specified and as directed232.00CumExcess(+)1Full ConversionINR0.000.00INR Zero Only
2.00Returning, filling in, including, spreading, leveling, watering and well ramming in layers not exceeding 25cm deep as in any type of soil complete all as specified and as directed139.00CumExcess(+)1Full ConversionINR0.000.00INR Zero Only
3.00Removing excavated materials to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point in any type of soil including spreading in low lying area and leveling complete all as specified and as directed93.00CumExcess(+)1Full ConversionINR0.000.00INR Zero Only
4.00Supply and laying burnt bricks of sub-class 'B' designation 75 of size 230x115x75mm laid in trenches for cable protection complete all as specified and as directed2200.00EachExcess(+)1Full ConversionINR0.000.00INR Zero Only
5.00M&L for fine dry river sand cushioning by laying 8cm thick layer below the cable for making soft bed and 15cm above the cable and then punning down to its consolidated thickness of 18cm after the cable is laid all as specified in SSR Part-I complete all as specified and as directed Note: Only punned thickness of sand shall be considered for measurement purposes34.20CumExcess(+)1Full ConversionINR0.000.00INR Zero Only
6.00Supplying, fixing / laying steel water tubing, medium grade, galvanised with screwed and socketed joints, in any length, including supply and fixing all fittings viz. bends, elbows, tees, short pieces, connectors, backnuts, diminishing pieces, caps, plugs, unions, flange, etc. ISI marked conforming to IS -1239 and fixed to walls or laid in floors / trenches for water connections including all necessary welding, etc. as required at site complete all as specified and as directed for the following bores:
7.00100mm20.00RmExcess(+)1Full ConversionINR0.000.00INR Zero Only
8.0080mm30.00RmExcess(+)1Full ConversionINR0.000.00INR Zero Only
9.0050mm50.00RmExcess(+)1Full ConversionINR0.000.00INR Zero Only
10.00Supply, laying, jointing, connecting and testing XLPE insulated PVC sheathed cable 1100V grade, screwed PVC bedded, armoured electric power cable, heavy duty multi-stranded aluminium conductor laid in trenches / fixed on walls/poles, passing through pipes, etc. including connecting up to DBs, etc. with required lugs, end terminal / cable glands complete all as specified and as directed of the following sizes: Note: Excavation and earthwork will be measured and paid separately under respective item herein
11.004 core 16 sqmm340.00RmExcess(+)1Full ConversionINR0.000.00INR Zero Only
12.003.5 core 50 sqmm230.00RmExcess(+)1Full ConversionINR0.000.00INR Zero Only
13.003.5 core 75 sqmm200.00RmExcess(+)1Full ConversionINR0.000.00INR Zero Only
14.003.5 core 95 sqmm150.00RmExcess(+)1Full ConversionINR0.000.00INR Zero Only
15.003.5 core 120 sqmm150.00RmExcess(+)1Full ConversionINR0.000.00INR Zero Only
16.003.5 core 185 sqmm100.00RmExcess(+)1Full ConversionINR0.000.00INR Zero Only
17.003.5 core 240 sqmm120.00RmExcess(+)1Full ConversionINR0.000.00INR Zero Only
18.00M&L for cable jointing kit for 1100V grade cable for straight through heat shrink type joint with jointing material and accessories suitable for the following sizes , XLPE insulated armoured aluminium conductor cable , complete all as specified and as directed
19.002/4 core x10 to16sqmm4.00EachExcess(+)1Full ConversionINR0.000.00INR Zero Only
20.003.5/4 core x 25 to 50sqmm2.00EachExcess(+)1Full ConversionINR0.000.00INR Zero Only
21.003.5/4 core x 70 to 120sqmm2.00EachExcess(+)1Full ConversionINR0.000.00INR Zero Only
22.003.5/4 core x 150 to 185sqmm2.00EachExcess(+)1Full ConversionINR0.000.00INR Zero Only
23.003.5/4 core x 240 to 400sqmm2.00EachExcess(+)1Full ConversionINR0.000.00INR Zero Only
24.00S&F in repairs of MCCB of the following capacity as mentioned herein below of, 415V, AC, Ics=100%Icu, 80 to 100% overload protection, adjustable type, with thermal magnetic release mechanism, breaking capacity 16kA including all necessary lugs, wire, etc. required for connecting up complete all as specified and as directed
25.00400A , 4 pole2.00EachExcess(+)1Full ConversionINR0.000.00INR Zero Only
26.00250A,4 pole2.00EachExcess(+)1Full ConversionINR0.000.00INR Zero Only
27.00250A, 3 pole3.00EachExcess(+)1Full ConversionINR0.000.00INR Zero Only
28.00200A, 3 pole4.00EachExcess(+)1Full ConversionINR0.000.00INR Zero Only
29.00200A, 4 pole4.00EachExcess(+)1Full ConversionINR0.000.00INR Zero Only
30.00125A, 4 Pole5.00EachExcess(+)1Full ConversionINR0.000.00INR Zero Only
31.0063A, 4 pole5.00EachExcess(+)1Full ConversionINR0.000.00INR Zero Only
32.00Supply & replace 3Ph LED Ammeter Cl 1digital type, 96X96 mm square Flush mounted case , Accuracy Class 1.0, with Inbuilt selector switch for 3 phase meters, Input voltage measurement range 50-520 VAC (P-P) , Aux supply 80-300 VAC, all complete with necessary wiring in the panel,complete all as specified and as directed.15.00EachExcess(+)1Full ConversionINR0.000.00INR Zero Only
33.00Supply & replace 3Ph LED Voltmeter Cl 1, digital type, 0-500V, 96X96 mm square Flush mounted case Accuracy Class 1.0, with Inbuilt selector switch for 3 phase meters, Input voltage measurement range 50-520 VAC (P-P) , Aux supply 80-300 VAC, all complete with necessary wiring, complete all as specified and as directed.15.00EachExcess(+)1Full ConversionINR0.000.00INR Zero Only
34.00Supply & replace resin cast wound/ring type CT 400A / 5A class 1.0 in 433 Volt LT panel boards after disconnectiong the old ones from site all complete as specified and as directed. 6.00EachExcess(+)1Full ConversionINR0.000.00INR Zero Only
35.00Supply and replace rotating phase selector switch for voltmeter and ammeter complete all as specified and as directed. 20.00EachExcess(+)1Full ConversionINR0.000.00INR Zero Only
36.00Supply and replace Copper lugs suitable for the following sizes including nuts, bolts and washers complete all as specified and as directed.
37.002.5sqmm30.00EachExcess(+)1Full ConversionINR0.000.00INR Zero Only
38.006sqmm30.00EachExcess(+)1Full ConversionINR0.000.00INR Zero Only
39.0016sqmm25.00EachExcess(+)1Full ConversionINR0.000.00INR Zero Only
40.0025sqmm25.00EachExcess(+)1Full ConversionINR0.000.00INR Zero Only
41.0035sqmm30.00EachExcess(+)1Full ConversionINR0.000.00INR Zero Only
42.00S&F in repair of Control Wiring for voltmeters and Ammeters with 1 Core , 2.5 Sq mm copper cable , complete all as specified and as directed.30.00RmExcess(+)1Full ConversionINR0.000.00INR Zero Only
43.00S&F in repair of Control Wiring for voltmeters and Ammeters with 1 Core , 6 Sq mm copper cable , complete all as specified and as directed.30.00RmExcess(+)1Full ConversionINR0.000.00INR Zero Only
44.00S&F in repair of Control Wiring for voltmeters and Ammeters with 1 Core , 16 Sq mm copper cable , complete all as specified and as directed.20.00RmExcess(+)1Full ConversionINR0.000.00INR Zero Only
45.00S&F in repair of Control Wiring for voltmeters and Ammeters with 1 Core , 25 Sq mm copper cable , complete all as specified and as directed.20.00RmExcess(+)1Full ConversionINR0.000.00INR Zero Only
46.00S&F in repair of Control Wiring for voltmeters and Ammeters with 1 Core , 35 Sq mm copper cable , complete all as specified and as directed.20.00RmExcess(+)1Full ConversionINR0.000.00INR Zero Only
47.00M&L for repairs and replacement of LT panels door hinges, mild steel of suitable size including cutting and welding and brazing complete all as specified and as directed.25.00Each JobExcess(+)1Full ConversionINR0.000.00INR Zero Only
48.00M&L for painting of LT panels at site and applying two coat of synthetic enameled grey paint after removing all dust & rust and paint shall confirm to IS 2032 , complete all as specified and as directed.250.00SqmExcess(+)1Full ConversionINR0.000.00INR Zero Only
49.00Supply, fabricated, install, test, and commissioning LT outdoor panel weather proof, dust/vermin proof, made out of 3.15mm thick CRCA sheet double openable door with angle iron frame and locking arrangement , including bus bar suitable for 3 phase 4 wire system, 415v, 50Hz, AC supply wth bus bar aluminium 300 Amps capacity including with PVC sleeves / taps RYB colours for phases indication, confirming to IP-54, and fixed on raised PCC platform with PCC 1:2:4, type B1 (20 mm graded aggregate) raised base with control wiring and compressing cable gland brass, copper/brass lugs etc confirming to CPRI approved manufacture , complete all as specified and directed by the Engineer-in-charge including and accommodating the followings: Note; All MCCBs are of thermal megnetic release with adjustable type overload protection, shortcircuit protection. (a) MCCB 4 pole 160 Amps 50Hz, 415 V,36 KA -01 no (for incoming) (b) TPN Bus bar Aluminium 300 Amp-01 (outgoing), mounted on hygroscopic insulator duly colour coded RYB & Green sleeves (c) LED type three Phase indicator with controlling fuses for RYB -01 set (d) 3 Phase Digital panel meter for Amp,Volt,KWH, power factor and other parameter flush mounting of size 96 x96 mm,Current Transformer of suitable rating - Set of three (e) LED type three Phase indicator with controlling fuses for RYB -01 set3.00EachExcess(+)1Full ConversionINR0.000.00INR Zero Only
50.00Supply, fabricated, install, test, and commissioning LT outdoor panel weather proof, dust/vermin proof, made out of 3.15mm thick CRCA sheet double openable door with angle iron frame and locking arrangement , including bus bar suitable for 3 phase 4 wire system, 415v, 50Hz, AC supply wth bus bar aluminium 600 Amps capacity including with PVC sleeves / taps RYB colours for phases indication, confirming to IP-54, and fixed on raised PCC platform with PCC 1:2:4, type B1 (20 mm graded aggregate) raised base with control wiring and compressing cable gland brass, copper/brass lugs etc confirming to CPRI approved manufacture , complete all as specified and directed by the Engineer-in-charge including and accommodating the followings: MAKE: L&T/ Milestone/ Advance/ Unilec/ C&S/ Schneider /any CPRI approved manufacturer Note; All MCCBs are of thermal megnetic release withadjustable type overload protection, shortcircuit protection. (a) MCCB 4 pole 400 Amps 50Hz, 415 V, 36 KA -01 no (for incoming) (b) MCCB 4 pole 250 Amps 50Hz, 415 V, 25 KA -01 no (for Outgoing) (c) MCCB 4 pole 160 Amps 50Hz, 415 V, 25 KA -02 no (for Outgoing) (d) MCCB 4 pole 100 Amps 50Hz, 415 V, 25 KA -02 no (for Outgoing) (e) LED type three Phase indicator with controlling fuses for RYB -01 set 2.00EachExcess(+)1Full ConversionINR0.000.00INR Zero Only
51.00(f) 3 Phase Digital panel meter for Amp,Volt,KWH, power factor and other parameter, selector switch flush mounting of size 96 x96 mm,Current Transformer of suitable rating - Set of three (g) Electrolyte Aluminium busbars PVC colour sleeved 600 Amps capacity TPN mounted on hygroscopic insulator duly colour coded RYB & Green sleeves
52.00Supply, fabricated, install, test, and commissioning LT outdoor panel weather proof, dust/vermin proof, made out of 3.15mm thick CRCA sheet double openable door with angle iron frame and locking arrangement , including bus bar suitable for 3 phase 4 wire system, 415v, 50Hz, AC supply wth bus bar aluminium 500 Amps capacity including with PVC sleeves / taps RYB colours for phases indication, confirming to IP-54, and fixed on raised PCC platform with PCC 1:2:4, type B1 (20 mm graded aggregate) raised base with control wiring and compressing cable gland brass, copper/brass lugs etc confirming to CPRI approved manufacture ,complete all as specified and directed by the Engineer-in-charge including and accommodating the followings: Note; All MCCBs are of thermal megnetic release withadjustable type overload protection, shortcircuit protection. (a) MCCB 4 pole 200 Amps 50Hz, 415 V, 36 KA -01 no (for incoming) (b) MCCB 4 pole 100 Amps 50Hz, 415 V, 25 KA -02 no (for Outgoing) (c) MCCB 4 pole 63 Amps 50Hz, 415 V, 25 KA -02 no (for Outgoing) (d) LED type three Phase indicator with controlling fuses for RYB -01 set (e) 3 Phase Digital panel meter for Amp,Volt,KWH, power factor and other parameter,selector switch flush mounting of size 96 x96 mm,Current Transformer of suitable rating - Set of three 2.00EachExcess(+)1Full ConversionINR0.000.00INR Zero Only
53.00(f) Electrolyte Aluminium busbars PVC colour sleeved 300 Amps capacity TPN mounted on hygroscopic insulator duly colour coded RYB & Green sleeves (g) Changeover onload type 200 Amps-01 No
54.00Supply, fabricated, install, test, and commissioning LT outdoor panel weather proof, dust/vermin proof, made out of 3.15mm thick CRCA sheet double openable door with angle iron frame and locking arrangement , including bus bar suitable for 3 phase 4 wire system, 415v, 50Hz, AC supply wth bus bar aluminium 300 Amps capacity including with PVC sleeves / taps RYB colours for phases indication, confirming to IP-54, and fixed on raised PCC platform with PCC 1:2:4, type B1 (20 mm graded aggregate) raised base with control wiring and compressing cable gland brass, copper/brass lugs etc confirming to CPRI approved manufacture ,complete all as specified and directed by the Engineer-in-charge including and accommodating the followings: Note; All MCCBs are of thermal megnetic release withadjustable type overload protection, shortcircuit protection. (a) MCCB 4 pole 350 Amps 50Hz, 415 V, 36 KA -01 no (for incoming) (b) MCCB 4 pole 100 Amps 50Hz, 415 V, 25 KA -02 no (for Outgoing) (c) MCCB 4 pole 63 Amps 50Hz, 415 V, 25 KA -02 no (for Outgoing) (d) LED type three Phase indicator with controlling fuses for RYB -01 set (e) 3 Phase Digital panel meter for Amp,Volt,KWH, power factor and other parameter, selector switch flush mounting of size 96 x96 mm,Current Transformer of suitable rating - Set of three (f) Electrolyte Aluminium busbars PVC colour sleeved 500 Amps capacity TPN and mounted on hygroscopic insulator duly colour coded RYB & Green sleeves 1.00EachExcess(+)1Full ConversionINR0.000.00INR Zero Only
55.00Supply, fabricated, install, test, and commissioning LT outdoor panel weather proof, dust/vermin proof, made out of 3.15mm thick CRCA sheet double openable door with angle iron frame and locking arrangement , including bus bar suitable for 3 phase 4 wire system, 415v, 50Hz, AC supply wth bus bar aluminium 300 Amps capacity including with PVC sleeves / taps RYB colours for phases indication, confirming to IP-54, and fixed on raised PCC platform with PCC 1:2:4, type B1 (20 mm graded aggregate) raised base with control wiring and compressing cable gland brass, copper/brass lugs etc confirming to CPRI approved manufacture ,complete all as specified and directed by the Engineer-in-charge including and accommodating the followings: Note; All MCCBs are of thermal megnetic release withadjustable type overload protection, shortcircuit protection. (a) MCCB 4 pole 100 Amps 50Hz, 415 V, 36 KA -01 no (for incoming) (b) MCCB 4 pole 63 Amps 50Hz, 415 V, 25 KA -02 no (for Outgoing) (c) MCCB 4 pole 40 Amps 50Hz, 415 V, 25 KA -02 no (for Outgoing) (d) LED type three Phase indicator with controlling fuses for RYB -01 set (e) 3 Phase Digital panel meter for Amp,Volt,KWH, power factor and other parameter, selector switch flush mounting of size 96 x96 mm,Current Transformer of suitable rating - Set of three (f) Electrolyte Aluminium busbars PVC colour sleeved 300 Amps capacity TPN mounted on hygroscopic insulator duly colour coded RYB & Green sleeves (g) Changeover onload type 250 Amps-01 No2.00EachExcess(+)1Full ConversionINR0.000.00INR Zero Only
56.00Supply, fabricated, install, test, and commissioning LT outdoor panel weather proof, dust/vermin proof, made out of 3.15mm thick CRCA sheet double openable door with angle iron frame and locking arrangement , including bus bar suitable for 3 phase 4 wire system, 415v, 50Hz, AC supply wth bus bar aluminium 600 Amps capacity including with PVC sleeves / taps RYB colours for phases indication, confirming to IP-54, and fixed on raised PCC platform with PCC 1:2:4, type B1 (20 mm graded aggregate) raised base with control wiring and compressing cable gland brass, copper/brass lugs etc confirming to CPRI approved manufacture , complete all as specified and directed by the Engineer-in-charge including and accommodating the followings: Note; All MCCBs are of thermal megnetic release withadjustable type overload protection, shortcircuit protection. (a) MCCB 4 pole 250 Amps 50Hz, 415 V, 36 KA -01 no (for incoming) (b) MCCB 4 pole 160 Amps 50Hz, 415 V, 36 KA -01 no (for Outgoing) (c) MCCB 4 pole 100 Amps 50Hz, 415 V, 25 KA -01 no (for Outgoing) (d) MCCB 4 pole 63 Amps 50Hz, 415 V, 25 KA -02 no (for Outgoing) (e) LED type three Phase indicator with controlling fuses for RYB -01 set 1.00EachExcess(+)1Full ConversionINR0.000.00INR Zero Only
57.00(f) 3 Phase Digital panel meter for Amp,Volt,KWH, power factor and other parameter flush mounting of size 96 x96 mm,Current Transformer of suitable rating - Set of three (g) Electrolyte Aluminium busbars PVC colour sleeved 400 Amps capacity TPN mounted on hygroscopic insulator duly colour coded RYB & Green sleeves
58.00Taking Down LT panel/Distribution boxes of any type , any size and any capacity from their existing place and further disposal all as specified and directed by Engr-in-charge.11.00EachExcess(+)1Full ConversionINR0.000.00INR Zero Only
59.00Taking Down LT panel any ype , any size and any capacity from their existing place and Refix the same one in other place including making good the disturbed surface whatever required(as per the existing condition) all as specified and directed by Engr-in-charge.Note-Connecting item like cables, lugs, joints are paid seperatly on heir respecive item of this schedule2.00EachExcess(+)1Full ConversionINR0.000.00INR Zero Only
60.00Supply and replace spreder terminal suitable for up to 4 pole 400 amps including nuts, bolts and washers complete all as specified and as directed. 11.00EachExcess(+)1Full ConversionINR0.000.00INR Zero Only
61.00M&L for repairs and replacement of door latches for LT panels of suitable size including cutting and welding and brazing complete all as specified and directed by Engineer-in-Charge.15.00EachExcess(+)1Full ConversionINR0.000.00INR Zero Only
62.00Supply and fixing including taking down copper strip 20mm x 3.15 mm with fixing screws for conductors/ earth lead including brazing and nut bolts jointing at all joints for building/ equipment laid through pipe/ trench/ surface complete all as specified and directed.160.00RmExcess(+)1Full ConversionINR0.000.00INR Zero Only
63.00S&F in repairs Anodised aluminium bus bar of required size as per site, after making necessary modifications in existing feeder pillar, change over switch, etc. with necessary lugs complete all as specified and as directed10.00KgExcess(+)1Full ConversionINR0.000.00INR Zero Only
64.00M&L for brick work with sub class "B" bricks, straight or curved on plan exceeding 6 m mean radius built in Cement Mortar 1:6 complete all as specified and as directed.4.00CumExcess(+)1Full ConversionINR0.000.00INR Zero Only
65.00Material and labour for 15 mm thick rendering in cement mortar 1:4 on fair faces of brick masonry or concrete surface, finished the surfaces even and smooth with using extra cement complete all as specified and as directed.12.00SqmExcess(+)1Full ConversionINR0.000.00INR Zero Only
66.00M&L for earthing using GI earthing wire with galvanised steel earth plate electode 600x600x6mm thick buried directly in ground, earth pit not less than 2.25m deep below ground level connection to and including GI earth lead wire 4mm dia extended to 7.5m as earth lead by means of GI bolts, nuts, etc. with provision of charcoal and salt all as per electrical plate No. 3 of SSR Part-I including water arrangement with GI pipe 20mm dia (medium grade), earth lead protection pipe 15mm light grade with bends, elbow, etc. from earth plate to test point, excavation and earthwork in any type of soil, returning, filling, ramming and removing of soil to distance not exceeding 50m, make good to match with existing surface making PCC pit (earth chamber) having internal size 300x300x300mm and outer size 600x 600x600mm with RCC reinforced cover 50mm thick and testing on completion including making test points on wall as per SSR specifications, taking down and disposing off old earthing complete all as specified and as directed12.00EachExcess(+)1Full ConversionINR0.000.00INR Zero Only
67.00Notes for serial item No. 66: (i) The cost of GI earth continuity wire / strip with GI pipe 20mm medium grade upto 7.5m is deemed to be included (ii) The earth chamber to be constructed 0.5m from edge of earth pit with necessary watering arrangement. The cost for the same is deemed to be included in above item (iii) Earthing shall produce desired earth resistance values as directed by the Engineer-in-charge
Total in Figures0.000.00INR Zero Only
Quoted Rate in FiguresSelect0.00000.0000 Zero Only
Quoted Rate in WordsINR Zero Only