Bidhelp
Food Corporation of India||Head Quarters,FCI,MFPD
Food Corporation of India||Head Quarters,FCI,MFPD
AGM(EM)
Delhi QTY :

Items - Supply, Installation, Testing and Commissioning of 02 Nos. 750 kVA DG sets at FCI Headquarters, New Delhi.-2nd Call

Tender Details
Costs
Documents
BOQ

BoQ1

Item Rate BoQ
BoQ_Ver3.0Item RateNormalINR OnlyINR
Select, Excess (+), Less (-)
Tender Inviting Authority: AGM(EM)
Name of Work: Supply, Installation, Testing and Commissioning of 02 Nos. 750 kVA DG sets at FCI Headquarters, New Delhi.
Contract No: EM/01/2025-26
Bidder Name :
PRICE SCHEDULE (This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only )
Sl. No.Item DescriptionItem Code / MakeQuantityUnitsEstimated RateAddition / DeductionAddition / Deduction ValuesCurrency Convertion against each ItemQuoted Currency in INR / Other CurrencyBASIC RATE PER UNIT In Figures To be entered by the BidderExcise DutyVATFreight Charges ( Unloading & Stacking)Any Other Taxes/Duties/LeviesTOTAL AMOUNT TOTAL AMOUNT With TaxesTOTAL AMOUNT In Words
12345678910111213141516171819202122232425262728293031323334353637383940414243444546474849505152535455
1.1Supply, installation, Testing & Commissioning of 'Silent Type Diesel Generating set as per CPCB IV + or better norms along with having Prime Power Rating of KVA as below, 415 volts at 1500 RPM, 0.8 lagging power factor at 415 V suitable for 50 Hz, 3 phase system & for 0.85 Load Factor, including testing at factory and site with fuel, load for test and other necessary arrangements Complete as per CPWD specifications, should have QR code which should contain drawing, test report OEM manual,GeoTag of manufacturing location, rating plate as per relevant IS Code etc. and consisting of the followings: A) Diesel Engine: Turbocharged Diesel engine 4 stroke water cooled, multi cylinder, dynamically balanced fly wheel, electric start of suitable BHP at 1500 RPM suitable for above output of alternator at 40 Degree C, 50% RH & at 1000 Meter MSL, capable of taking 10% over loading for one hour after 12 hours of continuous operation. The engine will be with Electronic governor, Dry type Air filter with service indicator, first filling of engine fuel (after commissioning) lubricating Oil, Coolant and other consumables complete with all the required accessories, the Electronic governor shall be as per ISO 8528.The engine shall comply to the latest CPCB norms (CPCB IV + or better) and Conforming to BS 5514, BS 649, IS 10000, IS 10002, IS 13018 and as per CPWD specifications.
1.2(B) Engine mounted Instrument Panel fitted with and having digital display for following: (i) Start-stop switch with key (ii) Water temperature indication (iii) Lubrication oil pressure indication (iv) Lubrication oil temperature indication (v) Battery charging indication and Voltage indication (vi) RPM indication (vii) Over speed indication (viii) Low lubricantion Oil trip indication 112 (ix) Engine Running Hours indication (x) Fuel Level C) Alternator: Synchronous alternator rated of appropriate KVA, 415 volts at 1500 RPM, 3 phase 50 Hz, AC supply with 0.8 lagging power factor at 40 Degree C, 50% RH & at 1000 Meter MSL. The alternator shall be having Screen Protected Drip Proof (SPDP) enclosure IP23, brushless, continuous duty, dynamically balanced rotor, capable of taking 10% over loading for one hour after 12 hours of continuous operation, self cooled,self-excited and self-regulated through AVR conforming to IS13364(Part 2)/IS: 4722/BS 2613 suitable for tropical conditions and with class- H insulation.
1.3D) FUELTANK: Daily service fuel tank of suitable liters capacity as per CPWD Specifications, fabricated out of 3 mm thick M.S. sheet complete with all standard accessories and fuel piping between fuel tank and diesel engine with MS class 'C' pipes of suitable dia. Complete with valves, level indications & accessories as required as per specifications E) Starting System: 12V/24V DC starting system comprising of starter motors: voltage regulator and arrangement for initial excitation complete with suitable numbers of batteries (180 AH capacity lead acid SMF type) as required as per specifications. The battery shall be housed inside the acoustic enclosure of DG Set. F) Acoustic and weather proof enclosure with arrangement for fresh air intake for cooling of the engine & alternator, extraction, discharging hot air in to the atmosphere and the temperature rise inside the enclosure, noise level outside enclosure. The acoustic enclosure should be suitable for cable connection/connection through bus-trunking. Such arrangements on acoustic enclosure should be water proof & dust-proof conforming to IP-65 protection. The enclosure shall be as per CPCB IV + or better norms etc. and as per CPWD specifications.
1.4750 KVAitem12.00Each0.00Excess(+)1Full ConversionINR0.000.00INR Zero Only1.01Supplying, Conveying and fixing spls. Including eartitem1123.223Nos
2Supply Installation, testing and commissioning of Cubical type floor mounted AMF sync panel made from 16 SWG Sheet Steel, duly pretreated, powder coated painted and aesthetically finished, suitable for controlling of 2*750KVA together along accessories as required. The panel shall be responsible for synchronised operation of both the DGs complying with specifications as mentioned below: Free standing floor mounted IP 42 automatic mains failure control panel including auto by-pass, suitable for KVA as below for silent type DG set complete with relays, timers, set of CTs for metering & protection and energy analyser to indicate currents, phase and line voltages, frequency, power factor, KWH, Kilo Volt Ampere Reative Hour (KVARH), KVA (Phase & Total), KW & provision for overload, short circuit, restricted earth fault, under frequency, power (aluminum) and control (copper ) cabling of suitable size upto 15 meter between AMF panel, LT Panel and DG Set including connection interconnection etc. as required, all complete and inter locking and communication/ Ethernet /RS485/SNMP port open protocol for BMS integration including suitable software, the panel shall be of DG Set OEM make etc. as per approved by Engineering in charge and including the following:1. Suitable numbers and appropriate capacity 4 pole motorised electrically operated draw out with cradle type 3 position ACB/ MCCB with electronic release for O/C & E/F and shunt trip.2. Auto/Manual/Test/Off selector switch 3. Protection for under and over voltage phase reversal (2 nos Over voltage relay, 2 Nos. reverse power relay and 2 Nos. under voltage relay). 4. 3 Sets of current transformers 15 P10 accuracy for protection and 15 VAclass-I for metering 5. Energy analyser unit to indicate current, Voltage( L-N & L- L), kW, kVA (Phase & Total), Frequency, KWH, PF. 6. LED Indicating lamps for load on mains and load on set. 7. Fuse/ MCB for instruments. 8. Battery charger, complete with transformer/ rectifier,D.C. voltmeter and ammeter, selector switch for trickle, off and boost and current adjustment.9. Main supply failure monitor. 10. Supply failure timer. 11. Restoration timer 12. Control unit with three impulse automatic engine start/stop and failure to start lockout. 13. Impulse counter with locking and reset facility. 14. ON/OFF/Control circuit switch with indicator15. Audio/Video annunciation for (i) High water temperature (ii) Low lubricating oil pressure (iii) Engine over speed (iv) Engine fails to start (v) Full load/maximum load warning 16. Protection for over/under Frequency, Loss of AC sensing, OverCurrent, Unbalancing load with suitable number of relays and accessories17. Maintenance notification based on Engine Run Hour & due date. 18. Load Management through PLC to achieve auto opening and closing of incomer breakers, bus coupler switching of essential panel , interlocking providing signal to AMF Panel for load status and AMF shall give command to DG Set to auto start / auto stop depending upon load status and requirement etc. and necessary hardware and software required to perform the operation shall be provided by the contractor including all control wiring.item21.00Each0.00Excess(+)1Full ConversionINR0.000.00INR Zero Only1.01Supplying, Conveying and fixing spls. Including eartitem1123.223Nos
3Supply of XLPE insulated aluminium armoured cable 3.5 C x 240 sq.mm Power Cableitem3440.00Metre0.00Excess(+)1Full ConversionINR0.000.00INR Zero Only
4Supply of XLPE insulated aluminium armoured cable 3.5 C x 185 sq.mm Power Cableitem4110.00Metre0.00Excess(+)1Full ConversionINR0.000.00INR Zero Only1.02Construction of chamber for 100mm sluice platesitem2213Nos
5Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp) size on wall surface as required.item5550.00Metre0.00Excess(+)1Full ConversionINR0.000.00INR Zero Only2Construction of chamber for 100mm sluices valveitem310Nos
6Supplying and making end termination with brass compression gland and aluminium lugs for 3½ X 185 sq. mm (57mm) size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. item612.00Each0.00Excess(+)1Full ConversionINR0.000.00INR Zero Only2Construction of chamber for 100mm sluices valveitem310Nos
7Supplying and making end termination with brass compression gland and aluminium lugs for 3½ X 240 sq. mm (62mm) size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. item78.00Each0.00Excess(+)1Full ConversionINR0.000.00INR Zero Only4Construction of chamber for 100mm sluice platesitem510Nos
8Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. item84.00Each0.00Excess(+)1Full ConversionINR0.000.00INR Zero Only
9Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. item94.00Each0.00Excess(+)1Full ConversionINR0.000.00INR Zero Only
10Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required. item1050.00Metre0.00Excess(+)1Full ConversionINR0.000.00INR Zero Only
11Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required. item1150.00Metre0.00Excess(+)1Full ConversionINR0.000.00INR Zero Only
12Supplying & Laying of 7 Core 2.5 Sqmm copper control cable for connecting AMF Panel and Generator. item12240.00Metre0.00Excess(+)1Full ConversionINR0.000.00INR Zero Only
13PCC Foundation with the ratio of 1:2:4 shall be provided. The length and breadth of the foundation shall be 300 mm more from the respective length*breadth of the Power Generator. 300 mm of this foundation height should be above the ground level. item1312.92Cum0.00Excess(+)1Full ConversionINR0.000.00INR Zero Only
14Supply and installation of exhaust gas piping of suitable dia 10" MS class B pipe incl. all necessary bend supports and clamps anti vibration mounting insulation of exhaust system with aluminium claddingitem14110.00Metre0.00Excess(+)1Full ConversionINR0.000.00INR Zero Only
15Supply and installation of exhaust gas piping of suitable dia 6" MS class B pipe incl. all necessary bend supports and clamps anti vibration mounting insulation of exhaust system with aluminium claddingitem1526.00Metre0.00Excess(+)1Full ConversionINR0.000.00INR Zero Only
16Supply & Installation of MS Steel Fabricated structure support for exhaust pipe.item165500.00kg0.00Excess(+)1Full ConversionINR0.000.00INR Zero Only
17Supply, Installation & Fabrication of Stainless steel sheditem171200.00kg0.00Excess(+)1Full ConversionINR0.000.00INR Zero Only
18Supply & Installation of Arcylic sheet for shed item18550.00kg0.00Excess(+)1Full ConversionINR0.000.00INR Zero Only
19Dismantling of Old pipes and DG Setitem191.00job0.00Excess(+)1Full ConversionINR0.000.00INR Zero Only
20Credit items:
20.1Buyback of old 100 KVA DG item20.11.00each0.00Less(-)-1Full ConversionINR0.000.00INR Zero Only
20.2Buyback of old 200 KVA DG item20.21.00each0.00Less(-)-1Full ConversionINR0.000.00INR Zero Only
20.3Buy back of Old dismantled pipes, cables, etcitem20.31.00lot0.00Less(-)-1Full ConversionINR0.000.00INR Zero Only
Total in Figures0.000.00INR Zero Only
Quoted Rate in FiguresSelect%00 Zero Only
Quoted Rate in WordsINR Zero Only